Specifications (continued)
External Static
Pressure
Net Supply Air Flow
Gross Air Flow
Supply
Exhaust
Pa
in. W.C.
L/s
CFM
L/s
CFM
L/s
CFM
25
0.1
117
248
118
250
130
277
50
0.2
108
229
109
231
119
253
75
0.3
102
218
103
220
110
234
100
0.4
94
200
95
202
101
216
125
0.5
85
181
86
183
92
197
150
0.6
77
163
78
165
82
175
175
0.7
69
146
70
148
71
151
200
0.8
61
129
61
131
60
128
225
0.9
52
110
52
111
49
104
250
1
45
96
46
97
40
86
Supply Temperature Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C
°F
L/s
CFM
Watts
Efficiency %
Effectiveness %
Heating
0
32
55
118
106
61
71
0
32
75
160
132
58
65
0
32
87
185
150
55
62
-25
-13
57
120
105
58
72
VNT5200H1000 Ventilation Performance
VNT5200H1000 Energy Performance
Total Recovery Efficiency = 48%
ERV/HRV Ventilation Systems 69-2480EF—19
6
VNT5200H1000
AIR FLOW (L/S)
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
50
100
150
200
250
300
0
25
50
75
100
125
150
175
200
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
NET SUPPLY AIR FLOW
AIR FLOW (CFM)
EXTERNAL
STATIC
PRESSURE
(PA)
M32354
Содержание VNT5070E1000