Problem
Possible Cause or
Symptom
Test Procedure
Solution
• No Power to
Unit
• HRV/ERV
does not turn
on.
• Speed Control
green LED
light does not
come on.
• Main power is not
energized.
• HRV/ERV power
cord not fully
inserted.
• HRV/ERV or wall
control in the OFF
position.
• Poor contact
between
connections on
high, low voltage
and door switch.
• Check power connection,
fuses or circuit breakers.
• Ensure power cord is firmly
inserted.
• Ensure HRV/ERV and or
wall controls are in the ON
position.
• Remove all controls
connection leading to unit.
• Continuity test of the units
power cord.
• Consult certified
technician to insure
proper installation of
main power.
• Remove and re-insert
power cord firmly.
• Remove door and
locate the area were
the switch compresses
the door sealant. Insert
behind door sealant
a metal edge or small
screw to insure proper
contact between door
safety switch and
access door.
• Un-plug HRV/ERV,
remove access panel
from motor mounts
and press firmly on all
connections.
• Replace AC power cord.
• During motor
selection
on Speed
Control while
in balancing
mode unit
(shut off),
goes to low
speed) or
into(INTER
mode) once
the (+ / - )
buttons are
pressed.
• Speed Control
board not
responding.
• Balancing mode
has been locked.
• Un-plug unit for 30 seconds to
re-boot.
• Reactivate balancing mode
and select motor and press ( +
/ - ) buttons.
• On the Speed Control
press and hold both
the ( + / - ) buttons for
15 seconds or until
you receive a solid
green light. This will
reset HRV/ERV back to
factory default mode.
Note: Unit must be re-
balanced to ensure
maximum performance.
CAUTION: Servicing the ERV/HRV unit with its electrical circuitry can cause personal
injury. Always make sure that power to the unit is disconnected prior to making any
connections. Failure to disconnect the power could result in electrical shock. Service
should only be performed by a qualified service technician.
ERV/HRV Ventilation Systems 69-2480EF—19
35
Troubleshooting
Содержание VNT5070E1000