background image

HPSR10*

5

33-00331EF—08

Boiler Controls

Hydronic Panels are capable of managing boilers with DHW priority. The panel features two isolated end switches labeled 
Boiler and End Switch for TT outputs to the boiler. Two slide switches are available to provide simple programing of the 
end switches to meet the desired application. See the operational matrix below detailing functionality of the switches.

Additionally, this panel features a LOW LIMIT input which must be closed for pumps to be activated. This input comes 
with a factory installed jumper for cold start boiler operation when the controlling Aquastat has a HIGH LIMIT only. If the 
installed boiler requires warm up time then this jumper should be removed and wired to the boiler.

Fig. 11. 

Fig. 12. 

Fig. 13. 

T-STAT

CALL

STATUS OF

ZR/ZC

CLOSED

BOILER RELAY=ON

END SWITCH=ON

ZONE PUMP=OFF

OPEN

NO PRIORITY ZONE OR PRIORITY END SWITCH

BOILER RELAY=ON

END SWITCH=ON

ZONE PUMP=ON

M37144

T-STAT

CALL 

STATUS OF

ZR/ZC

OPEN

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = ON

IS THIS THE

PRIORITY ZONE? 

DEACTIVATE ALL

OTHER ZONES 

YES

IS PRIORITY

ACTIVE? 

NO

NO

WAIT FOR

PRIORITY ZONE

TO SATISFY  

YES

CLOSED

PRIORITY ZONE, NO PRIORITY END SWITCH

M37145

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = OFF

M37146

T-STAT

CALL

STATUS OF

ZR/ZC

CLOSED

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = ON

IS THIS THE

PRIORITY ZONE? 

DEACTIVATE ALL

OTHER ZONES 

YES

IS PRIORITY

ACTIVE? 

NO

NO

WAIT FOR

PRIORITY ZONE  

TO SATISFY

YES

STATUS OF

ZR/ZC

CLOSED

OPEN

OPEN

PRIORITY ZONE, PRIORITY END SWITCH

BOILER RELAY = ON

END SWITCH = ON

ZONE PUMP = OFF

BOILER RELAY = ON

END SWITCH = OFF

ZONE PUMP = ON

BOILER RELAY = ON

END SWITCH = OFF

ZONE PUMP = OFF

Содержание HPSR10 Series

Страница 1: ...essionals only PANEL SPECIFICATIONS Table 1 NOTES All circulator relay connections including ZC ZR are rated for 5A full load and 30A locked rotor 1 6 to 1 2HP depending on technology at 120VAC Check...

Страница 2: ...screws in Fig 3 Din Rail Flow 1 Mount the DIN rail as per manufacturers instruc tions Fig 4 2 Hang panel by the tabs on the rail s top edge Fig 5 3 Snap into rail by pressing the bottom of panel again...

Страница 3: ...power to electronic thermostats NOTE It is up to the installer to ensure that the 40VA per transformer limit is not exceeded Additionally Hydronic Panels are compatible with Equipment Interface Modul...

Страница 4: ...6 Power Boiler End Switch HWSR506 6 ZONE PUMP CONTROLLER ZR ZC 2 AMP TRANSFORMER FUSE ZONE 1 FUSE ZONE 2 FUSE ZONE 3 FUSE ZONE 4 FUSE ZONE 5 FUSE PRIORITY END SWITCH PRIORITY END SWITCH PRIORITY ZONE...

Страница 5: ...wired to the boiler Fig 11 Fig 12 Fig 13 T STAT CALL STATUS OF ZR ZC CLOSED BOILER RELAY ON END SWITCH ON ZONE PUMP OFF OPEN NO PRIORITY ZONE OR PRIORITY END SWITCH BOILER RELAY ON END SWITCH ON ZONE...

Страница 6: ...calling for heat Table 2 Color Chart REGULATORY INFORMATION This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful...

Страница 7: ...ar des professionnels seulement SP CIFICATIONS DU PANNEAU Tableau 1 REMARQUE Tous les raccordements du relais du circulateur y compris les ZC ZR sont adapt s un rotor bloqu de 30 A et une charge nomin...

Страница 8: ...ail DIN 1 Montez le rail DIN conform ment aux instructions du fabricant Fig 4 2 Suspendez le panneau par les languettes sur le bord sup rieur du rail Fig 5 3 Embo tez le panneau dans le rail en appuya...

Страница 9: ...troniques qui ont besoin de l alimentation REMARQUE il incombe l installateur de veiller ce que la limite de 40 VA par transformateur ne soit pas d pass e En outre les panneaux hydroniques sont compat...

Страница 10: ...SIBLE ZONE 1 FUSIBLE ZONE 2 FUSIBLE ZONE 3 FUSIBLE ZONE 4 FUSIBLE ZONE 5 INTERRUPTEUR D EXTR MIT PRIORITAIRE INTERRUPTEUR D EXTR MIT PRIORITAIRE ZONE PRIORITAIRE ZONE 1 PRIORIT ZONE 2 ZONE 3 ZONE 4 ZO...

Страница 11: ...CHAUDI RE MARCHE INTERRUPTEUR D EXTR MIT MARCHE POMPE DE LA ZONE MARCHE OUVERT RELAIS DE LA CHAUDI RE MARCHE INTERRUPTEUR D EXTR MIT MARCHE POMPE DE LA ZONE ARR T MF37144 ZONE PRIORITAIRE AUCUN INTER...

Страница 12: ...as causer d interf rences dangereuses et 2 ce dispositif ne doit accepter aucune interf rence re ue notamment les interf rences l origine d un fonctionnement ind sirable Couvercle en mylar Fig 15 Couv...

Отзывы: