AQUATROL ZONE SYNCHRONIZING INJECTION/MIXING BOILER RESET CONTROLS

7

69-1990—03

When a new AQ2000 component is connected on the 
AQUATROL network, its settings are communicated to the 
AQ252's Boiler Control Module (AQ15200B) within 10 
seconds of being connected. If the component is an 
AQ1000 thermostat, the setpoints for that zone 
thermostat can be modified from the Boiler Control 
Module as soon as it is recognized by the Control Module. 

When an AQ thermostat is disconnected from the 
AQUATROL network, a message displays on the System 
Status page of the AQ252 indicating “Lost Zone A-xx”, 
where “xx” is the specific identity, or address, of the lost 
zone. This helps the servicing contractor quickly identify 
the lost zone and fix its wiring, to re-establish 
communication with the Control Module.

LOST ZONE A-1

         …

LOST ZONE D-16

n/a

Lost communication with a zone (A-1 to A-16, B-1 to B-16, C-1 to C-16, or D-1 to D-
16).

MIN. RETURN PROT

n/a

The temperature measured by the return sensor is at or below the minimum return 
water temperature.

NO DHW PROBE

n/a

No DHW sensor connected or it is defective.

NO LINE VOLTAGE

n/a

No line voltage has been detected on the N and L terminals on the line voltage input 
to the control module.

NO OUTDOOR PROBE

n/a

No outdoor sensor connected or it is defective.

NO RETURN PROBE

n/a

No return sensor connected or it is defective.

NO SECOND. PROBE

n/a

No secondary (mixed) loop sensor connected or it is defective.

NO SUPPLY PROBE

n/a

No supply sensor connected or it is defective.

SHORT CYCLE PROT

n/a

There is a call for heat, but less than two minutes have elapsed since the last firing 
of the boiler (prevents short cycling).

VALVE INIT

n/a

Motorized mixing valve controlling the secondary loop is being initialized and 
repositioned (opening or closing) to meet the secondary loop target temperature.

WATER READY

n/a

Boiler Supply Water temperature is at or above the target temperature calculated by 
the AQ252.

WWSD ACTIVE

n/a

Zone calls for heat is not served because WWSD (Warm Weather Shutdown) is in 
progress.

Table 2. LCD Status Notices and Error Messages. (Continued)

LCD Display

Parameter

Meaning

Содержание AQUATROL AQ252

Страница 1: ...icians should service this Control Panel The front cover of the AQ251 Control Panel should not be removed as this will expose the user to potentially dangerous line voltage 120V electricity Congratula...

Страница 2: ...alue will decrease increase by pressing these buttons When holding the or button for more than a second the values automatically decrease increase at a faster pace similar to setting the time on a dig...

Страница 3: ...dule you must use the or button to change the time 2 The OK button when pressed defaults the time setting to midnight If the active menu item leads to a further sub menu pressing the OK button display...

Страница 4: ...n this sub menu are The temperature scale for the display Fahrenheit or Celsius for both the AQ252 control s LCD and the zone thermostats The time display in 12 hour e g 7 00 PM or 24 hour format e g...

Страница 5: ...AKE program time for all days the LEAVE program time for all days etc When all four programs have been set select the COPY TO ALL DAYS option This displays the prompt COPY TO ALL DAYS ARE YOU SURE Sel...

Страница 6: ...OFF time has not yet elapsed A C MIN ON TIME n a The A C compressor is active and the minimum ON time has not yet elapsed AUX IN EM SHUT n a Auxiliary Input s Emergency Shut Down is active BOILER EM S...

Страница 7: ...the return sensor is at or below the minimum return water temperature NO DHW PROBE n a No DHW sensor connected or it is defective NO LINE VOLTAGE n a No line voltage has been detected on the N and L t...

Страница 8: ...RETURN PROBE NO SECOND PROBE NO SUPPLY PROBE SHORT CYCLE PROT VALVE INIT WATER READY WWSD ACTIVE SYSTEM STATUS 1 ZONE A 1 ROOM TEMP FLOOR TEMP SETPOINT 70 FLOOR SETPT 70 HEAT COOL STATUS SETBACK 7 SET...

Отзывы: