4-10.
OTHER ELECTRICAL
Circuit breaker inspection
There should be continuity between the terminals
with the circuit breaker in the ON position and no
continuity with the circuit breaker in the OFF
position.
Voltmeter inspection
Check the position to the pointer of Voltmeter.
Pointer position
120V
:
110V to 130V.
220V
:
210V to 230V.
230V
:
220V to 240V.
Terminal inspection
Make sure that the connector does not break the
cover.
Check that the female terminal does not open
too much.
If rusting occurs on the terminals, correct with
sand paper before connecting.
Fuse inspection
If the over current, the fuse will be damage.
Check visually for damage.
ON
OFF
50