No anticipation

 

 

3-5  

Normal 

anticipation

 

 

10  

Maximum 

anticipation 

 
The following settings are recommended: 
 
Forced air systems: 4 

 

Radiant systems: 6 
 
A lower setting will decrease the tendency to turn off the heating system before the desired heat setting is 
reached.  If the heating system response time is slower, as are most radiant heating systems, a higher number 
will help maintain an even space temperature. 
 
The default setting is 4. 
 

11  Cooling minimum on/off time (minutes)

 

 
This item is used to limit the on and off times of the cooling system.  When the cooling system starts, it must 
remain on for the minimum time set by this item.  When the cooling system turns off, it must remain off for a 
minimum time set by this item.   
 

Setting 

Cycles per hour (maximum) 

5 6 
6 5 
7 4 
8 3.7 

10 3 

 
The recommended setting is 8 minutes.  A higher setting may be appropriate for buildings with low heat 
loss/gain.  The default setting is 8. 
 

12  Heating minimum on/off time (minutes)

 

 
This item is the same as the “Cooling minimum on/off time”, but for heating.  The default setting is 8. 
 

13 Not 

used

 

 

14 Clock 

adjust

 

 
If the clock on the thermostat is running faster or slower than the actual time, you can have the thermostat 
automatically compensate up to 29 seconds per day.  The thermostat will add or subtract the selected amount of 
time daily. 
 
(1 = “- 29” to 59 = “+ 29” seconds per day; 30 = No change) 

 

The default setting is 30. 

Содержание O M N I S T A T RC-90BZ

Страница 1: ...table in the country in which this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully Read the Owner s Manual carefully 2...

Страница 2: ...ING When mounting the RC 90BZ grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark t...

Страница 3: ...tat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accurate temperature reading by the thermostat Align the tabs of the thermostat face w...

Страница 4: ...he Fan key 2 times POWER UP 1 Double check wiring be sure that there are no stray wires or wire strands at the connections 2 Connect power to the control transformer and system The display will show a...

Страница 5: ...5 5 Figure 5 Installation as a Master thermostat...

Страница 6: ...6 6 Figure 6 Installation as a Slave thermostat Figure 7 Installation as a Zone thermostat with separate transformer Required by some zone panels...

Страница 7: ...m HEAT COOL or OFF CONFIGURING THE BACKLIGHT ON THE RC 90BZ The backlight on the RC 90BZ can be configured to one of three different modes 1 on for 30 seconds when a key is pressed 2 always on or 3 al...

Страница 8: ...its in the center of the display are the value of the item number 3 Press the Prog key to advance to the next item 4 Press the Hold key to return to the previous item 5 Use the arrow keys to change th...

Страница 9: ...0 Auto changeover no fan with heat 1 Auto changeover fan on with heat 4 Manual changeover no fan with heat 5 Manual changeover fan on with heat 12 Heat only no fan with heat 13 Heat only fan on with h...

Страница 10: ...this setting The default setting is 91 07 Not used 08 Not used 09 Cooling anticipator This item adjusts the tendency of the thermostat to run the cooling system to refresh and dehumidify the air befo...

Страница 11: ...ain on for the minimum time set by this item When the cooling system turns off it must remain off for a minimum time set by this item Setting Cycles per hour maximum 5 6 6 5 7 4 8 3 7 10 3 The recomme...

Страница 12: ...em was in operation this week 17 System runtime Last week This item logs the amount of time hours that the heating and cooling system was in operation last week QUICK REFERENCE SETUP GUIDE This table...

Страница 13: ...ary or inclusion controller to exclude the thermostat from the network press and release the Hold button on the thermostat This will exclude the thermostat from the Z Wave network The thermostat suppo...

Страница 14: ...LASS_THERMOSTAT_FAN_STATE Upon power up allow 10 seconds for the RC 90BZ thermostat to initialize After 10 seconds a controller can request the state of the fan COMMAND_CLASS_THERMOSTAT_OPERATING_STAT...

Страница 15: ...omply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential install...

Страница 16: ...tat keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check Node ID 2 Check communications mode setting Control By Remote System Not Working 34 Check setup of the remote system Ensure that all setu...

Отзывы: