IV. Storage and Installation
1. Storage
The inverter must be kept in its original package box before installation.
Pay attention to the followings when keeping it in storage if the inverter
is not used for the time being:
● It must be stored in a dry place without rubbish or dust.
● The suitable temperature for storage is between -20
℃
and +65
℃
.
● The relative humidity required is 0-95% without condensation.
● There is no corrosive gas or liquid in the storage ambience.
● It’s better to lay the inverter on a rack and keep it in a proper package.
● It is better not to store the inverter for long time. Long time storage of
the inverter will lead to the deterioration of electrolytic capacity. If it
needs to be stored for a long time make sure to power it up one time
within a year and the power-up time should be at least above five hours.
When powered up the voltage must be increased slowly with a voltage
regulator to the rated voltage value.
2. Installation Site and Environment
The inverter should be installed at the following location:
● Ambient temperature -5
℃
to 40
℃
with good ventilation.
● No water drop and low moisture.
● Free from direct sunshine, high temperature and heavy dust fall.
● Free from corrosive gas or liquid.
● Less dust, oil gas and metallic particles
● Free from vibration and easy for service and inspection.
● Free from the interference of electromagnetic noise.
Attention: The ambient conditions of the inverter will affect its
service life.
3. Installation and Direction
● There must be enough space left around the inverter for easy
maintenance and cooling. See Diagram 1.
● The inverter must be installed vertically with the smooth ventilation
for effective cooling.
● If there is any instability when installing the inverter, please put a flat
Содержание HLP-A Series
Страница 1: ......
Страница 2: ...HLP A Series...
Страница 3: ......
Страница 27: ...HLP A Series HLP A Series 22 1 Good 2 Good 3 Not good...
Страница 69: ...HLP A Series HLP A Series 64 The following is the block diagram of multi pumps operation...
Страница 106: ...HLP A Series HLP A Series 101 HLPA05D523B HLPA07D523B Unit mm HLPA05D543B HLPA07D543B Unit mm...
Страница 117: ......