5. Linkage of Multi Pumps
Attention:
①
The frequency of the main inverter can be set by the potentiometer.
②
The proportion relation of the inverters can be adjusted by CD068.
For example: For F
Inverter1
: F
Inverter2
: F
Inverter3
=1 : 2 : 3 the parameters of CD068 can
be adjusted.
Frequency 1 : CD068=50, Frequency 2 : CD068=100, Frequency 3 : CD068=150. In
case of the analog of 10V, the corresponding frequencies are respectively 50Hz,
100Hz, 150Hz with the proportion of .1 : 2 : 3.
③
For easy operation and adjustment a f ine tuning potentiometer can be
added. For concrete application please consult.