background image

Location and Mounting

1.

Determine the fan package location on the enclosure.  This location depends on the available

space within the enclosure and on the airflow pattern desired.  Allow clearance for the electrical

panel and mounting studs.  Follow the general fan package application guidelines outlined in the

Hoffman catalog.  Note:  Type 12 cooling fan package and exhaust grille are designed to be

installed on the vertical sides of the enclosure only.  Do not install these product on top of the

enclosure.

2.

UL Arc Barrier Requirement:  If a ventilation opening is less than 12 inches (305 mm) from an

arcing part, a barrier shall be interposed between the ventilation opening and a possible source

of arcing, such as a power

circuit switch, a fuse, the vent openings of a circuit breaker, a

conductor, or an overload relay.

A barrier shall be of such dimension and so located that any straight line drawn from any arcing

part past the edge of the barriers intersects a point in the ventilation opening plane that is at least

0.25 inches (6.35 mm) outside the edge of the ventilation opening.

A barrier shall be secured in place by mechanical means such as mechanical fasteners.

3.

Clear all wires and components out of the way and make the proper size cutout.  See the

following hole pattern and table.

4.

If electrical grounding is required, ground the fan housing using a lead wire sized per N.E.C.

standards.  Use the green grounding screw provided to connect the separate ground wire (not

supplied) to the fan grounding pad.

5.

Establish the airflow direction through the fan.  Arrows marked on the fan housing indicate the

airflow direction and blade rotation.  Reference the exploded view and note on the previous page.

6.

Guide the lead wires and the grounding wire through wire access hole in rear wall of plenum.

(models:  TFP61UL12, TFP62UL12, TFP101UL12, TFP102UL12 only)

7.

Mount the fan to the plenum with the supplied thread cutting screws.

8.

Mount steel wire finger guard to fan with supplied thread cutting screws.  (models:  TFP41UL12,

TFP42UL12 only)

9.

Insert the assembled fan package into the enclosure cutout with the gasket located between the

plenum and enclosure wall as shown.

10. Secure the fan package in place using the supplied screws, lockwashers, and nuts.
11. For models TFP61UL12, TFP62UL12, TFP101UL12, and TFP102UL12, snap

in finger guard and

insert filter over finger guard.  For models TFP41UL12 and TFP42UL12, insert filter into plenum.

12. Insert the filter (AFLTRXXUL12) so that the white fabric side is facing into the enclosure and the

foam side is facing out.

13. Snap

on grille over fan package.

87560859

 7 

E

 2005 Hoffman Enclosures Inc.

Barrier Material

Minimum Thickness

Steel

0.053 in.

1.35 mm

Aluminum

0.075 in.

1.9 mm

Polycarbonate

0.125 in.

3.2 mm

Other Non

metallic

0.250 in.

6.35 mm

Содержание TFP101UL12

Страница 1: ...Cooling Fan Package Type 12 Ventilateur de refroidissement Type 12 Paquete de Ventilador Tipo 12 87560859 Rev B 114313 P N 87746115 E 2005 Hoffman Enclosures Inc...

Страница 2: ...warning light to indicate high enclosure temperatures This temperature switch can also be used to cycle the cooling fans as cooling requirements change Wiring 1 All wiring must comply with applicable...

Страница 3: ...e ou un voyant d avertissement pour indiquer les temp ratures lev es de l enceinte On peut aussi utiliser ce thermocontact pour faire fonctionner les ventilateurs de refroidissement en cycle selon les...

Страница 4: ...ras en la caja Este interruptor de temperatura se puede tambi n utilizar para completar un ciclo de ventiladores cuando las condiciones ambientales cambian Cableado 1 Todo el cableado debe hacerse de...

Страница 5: ...87560859 5 E 2005 Hoffman Enclosures Inc 2x 8x 1 4x 2 4x 3 4x 4 4x 5 4x 6 10 32x 50 No 8 M5x12 8 32x 50...

Страница 6: ...par ment El sistema requiere rejilla de salida de aire Tipo 12 Ordenar por Separado TEG4UL12 TEG6UL12 TEG10UL12 TFP61UL12 TFP62UL12 TFP101UL12 TFP102UL12 TFP41 TFP42 Gasket Joint d tanch it Empaque S...

Страница 7: ...le 4 If electrical grounding is required ground the fan housing using a lead wire sized per N E C standards Use the green grounding screw provided to connect the separate ground wire not supplied to t...

Страница 8: ...terre l aide d un fil de raccordement de calibre conforme aux normes du Code canadien de l lectricit Utiliser la vis de mise la terre verte pr vue pour raccorder le fil de terre distinct pas fourni l...

Страница 9: ...e de aterrizaje para conectar el cable separado de la tierra no incluido a la plataforma de aterrizaje del ventilador 5 Establecer la direcci n de circulaci n de aire a trav s del ventilador Las flech...

Страница 10: ...ber C D E F G TFP41UL12 TFP42UL12 5 66 In 144 5 66 In 144 4 12 In 105 6 39 In 162 77 In 20 TFP61UL12 TFP62UL12 7 16 In 182 7 16 In 182 4 50 In 114 7 89 In 200 1 33 In 34 TFP101UL12 TFP102UL12 11 16 In...

Страница 11: ...aisir les parties sup rieure et inf rieure de la grille Agarre la rejilla de la parte superior e inferior como lo muestra la foto 2 While pulling out push down Tirer vers l ext rieur et le bas en m me...

Страница 12: ...Britain Schroff UK Ltd Maylands Avenue Hemel Hempstead Herts HP2 7DE 44 01442 240471 www schroff co uk Sweden Schroff Scandinavia AB Box 2003 12821 Skarpn ck 46 08683 61 00 www schroff se France Schr...

Отзывы: