Installation, Operation and Maintenance Manual for Hoffman Purge/Pressurization Unit

 

Continuous Flow (CF) conforming to NFPA 496 

 

IMPORTANT NOTE It is essential, to ensure conformity with the standard, 

 

 

that the user of the unit observes the following instructions. 

Please refer to the latest standard for detailed requirements and definitions. 

 

Section 0 Description and Principle of Operation 

 

All Hoffman Purge/Pressurization Unit

 

pressurization units 

provide: 
 
a)  a  method  of  pressurizing  a  Pressurized  Enclosure  (PE) 
while  at  the  same  time  compensating  for  any  leakage, 
together with 
 
b) a method of purging the enclosure, before power is turned 
on, to remove any flammable gas that may have entered the 
enclosure while it was not pressurized. 
 
Continuous Flow Units, Model CF, allow air to flow through 
the PE continuously by having a fixed outlet aperture, which 
does not have any means of closure. The act of pressurizing 
the enclosure forces air to “leak” through the outlet aperture. 
The Control Unit admits sufficient air at the inlet to the PE to 
compensate for the air leaking out of the outlet aperture as 
well as from any other accidental leakage paths. The flow 
rate is constant both during purging and thereafter. The 
Purging Flow rate is monitored by a separate “Purge Flow 
Sensor” located in the CU, which detects the differential 
pressure across the purge flow orifice located directly before 
the Outlet Orifice. The Purge Flow Sensor is set to operate 
when the desired differential pressure is exceeded. The 
output from the Flow Sensor is indicated on the CU. 
 
Type Continuous Flow (CF) Units are comprised of the 
following major parts: 
 

- A Control Unit (CU) containing as a minimum, for “Y/Z” 
Pressurization, a Flow Control Valve (LCV), Minimum 
Pressure and Purge Flow sensing devices, and a 
“Pressurized”/”Alarm” indicator. The CU supplies a 
‘Pressurized’ signal showing whether the PE pressure is 
satisfactory or not. 
 
- A Relief Valve (RLV), fitted to the PE, to provide a means 
of limiting the maximum pressure experienced by the PE 
during operation. All RLVs incorporate a Spark Arrestor to 
prevent sparks being ejected from the PE through the RLV 
aperture. The RLV is fitted solely as a safety device and 
does not open in normal operation. 
 

-

An Outlet Orifice, which has been pre-calibrated so that 

the pressure drop at the desired flow rate is known. The 
Minimum Pressure Sensor within the CU will be set to the 
same figure as the pressure drop. When the PE pressure 
exceeds the calibrated pressure the Continuous Flow must 
be taking place.  The unit is provided with calibrated Outlet 
Orifices. Where the Outlet Orifice disk is removable and can 
be easily changed by the user to give different flow rates 
according to the size of the PE and the available air supply 
capacity.  
 
 
 

 

Section 1 Installation of the Unit 

 

The installation of the Hoffman Purge/Pressurization 
Unit, the protective gas supply, any alarm device should 
be in accordance with the requirements of NFPA 496. 
 
The electrical installation associated with the  
Hoffman Purge/Pressurization Unit shall conform to the 
local codes and the relevant clauses of NFPA 496. 
 
1.1  Installation of the Hoffman CF Unit 

 

1.1.1 The Hoffman Purge/Pressurization Unit should be 
installed either directly on or as close as possible to the 
Pressurized Enclosure (PE). It should be installed so that the 
unit indicators may be readily observed. 
 
1.1.2 All parts of any unit carry a common serial number. If 
installing more than one unit, ensure that this commonality is 
maintained on each installation. 
 
1.1.3 Any tubing, conduit and fittings used to connect to the 
PE should be metallic, or, if non-metallic, conform to the 
local codes for flammability ratings. No valve may be fitted in 
any tube connecting the Hoffman Purge/Pressurization Unit 
to the PE. 
 
1.1.4 The user or manufacturer of the PE shall determine the 
volume of the PE, the necessary purging volume, and the 
time to be allowed for purging, using the chosen Hoffman 
Purge/Pressurization Unit purging flow rate. It is the user's 

responsibility to verify or enter this data on the PE and/or 
unit nameplate. Ask Hoffman if in doubt. 
 
Example calculations: 
 
a) If the PE external dimensions give a volume of 20 cubic 
feet, and it is NOT a motor, multiply the volume by four to get 
the Purging Volume i.e. 80 cubic feet. Divide the Purging 
Volume by the purge rate e.g. 32 cubic feet per minute, and 
round up to the next even minute above, i.e. Purging time 
would be 4 minutes. 
 
b) If the PE is a motor, multiply the internal free volume by 
ten to get the Purging Volume. For the example above, 
Purging time would be 8 minutes. 
 
1.1.5 If the PE contains an internal source of release of 
flammable gas or vapor, the procedures for assessment of 
the release as given in NFPA 496 shall be observed. The 
user must verify that the specification of the Hoffman 
Purge/Pressurization Unit e.g. pressures, continuous flow 
(dilution) rate and type of protective gas are correct for the 
specific application.

 

 

 
1.1.6 More than one PE can be protected by a single unit. If 
PEs are connected and purged in “series” e.g. “Daisy 
Chained”, the Outlet Orifice must be fitted on the last 
enclosure with the Purge Inlet to the first enclosure. The RLV 
must be fitted to the last enclosure.

 

The bore and length of 

the tube or conduit used to interconnect the enclosures is 

Содержание PCFB1YZ

Страница 1: ...ication Sheet CF Y Z Purge Pressurization Unit 2 Application Suitability 3 Installation Operation and Maintenance for CF Units Section 0 Description and Principle of Operation Section 1 Installation o...

Страница 2: ...anada NFPA 496 UL E466718 Class I Div 1 Class I Div 2 Groups A B C D Groups A B C D For limitations and conditions of use refer to the applicable certificate at the back of this manual Supply Pressure...

Страница 3: ...t be fitted to the Pressurized Enclosure The following materials are used in the construction of Hoffman Purge Pressurization Units If substances that will adversely affect any of these materials are...

Страница 4: ...alibrated Outlet Orifices Where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply cap...

Страница 5: ...the PE Exception Power to Intrinsically Safe or other apparatus which is already suitable for the location need not be isolated by the Hoffman Purge Pressurization unit When utilizing Y Z Pressurizat...

Страница 6: ...the RLV and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor with a spare Check the condition of the air supply filter element Clean or replace it as necessary 3...

Страница 7: ...le cause 2 Excessive Pressurized Enclosure PE leakage Check around the PE when flow is taking place Any significant leakage must be cured Has a Leakage Test been done The total leakage should not exce...

Страница 8: ...Arrestor with circle clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air su...

Страница 9: ...Quick Installation Guide PCFF1YZ...

Страница 10: ...clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air supply to Control Unit 7...

Страница 11: ...Spark Arrestor Orifice Relief Valve Drawing...

Страница 12: ...Relief Valve Position Relief Valve Cutout Schematic for both PCFB1YZ and PCFF1YZ...

Страница 13: ...instructions and Article 504 of the NEC ANSI NFPA 70 3 For guidance on Installation see ANSI ISA RP12 6 Installation of IS Instrument Systems in Class I Hazardous Locations 4 Voc or Vt of associated a...

Страница 14: ......

Страница 15: ......

Страница 16: ...Hoffman Enclosures Inc 2100 Hoffman Way Anoka Minnesota 55303 1745 USA Phone 763 422 2211 www hoffmanonline com P N 89108870 Dwg 89109562 A...

Страница 17: ......

Отзывы: