2.  Application Suitability 

 

Hoffman Purge/Pressurization Units are certified for use in Hazardous Areas, where the 
Hazardous Area is non-mining (i.e. above ground) and the hazard is caused by flammable 
gasses, vapors or dust. 
 
Z-Purge Units may be used in IECEx, ATEX Zone 2(22) - Category 3 and NEC 500 Class I, Div 
2. 
 
Y-Purge Units may be used in IECEx, ATEX Zone 1(21) - Category 2 and NEC 500 
Class I, Div 1. 
 
Hoffman Purge/Pressurization Units may be used for hazards of any gas group. However, 
apparatus associated with the Hoffman Purge/Pressurization Unit, such as Non-Incendive, 
Intrinsically Safe signaling circuits and flameproof enclosures containing switching devices may 
be limited in their gas group. The certification documentation supplied with any such devices 
must be checked to ensure their suitability. 

 

This unit is designed for use primarily with compressed air. Where other inert compressed 
gasses are used (Nitrogen, for example) the user must take suitable precautions so that the 
buildup of the inert gas does not present a hazard to health. Consult the Control of Substances 
Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, 
a warning label must be fitted to the Pressurized Enclosure. 

 

The following materials are used in the construction of Hoffman Purge/Pressurization Units. If 
substances that will adversely affect any of these materials are present in the surrounding 
environment, please consult Hoffman for further guidance. 
 
Materials of construction: 
Stainless Steel 

Aluminum 

Acrylic 

Mild (carbon) Steel 

Nylon  

Silicone Rubber 

Brass   

Polyurethane   

Neoprene 

 
3. Installation, Operation and Maintenance for CF Units 
This Hoffman Purge/Pressurization Unit is designed for use under normal industrial conditions 
of ambient temperature, humidity and vibration. Please consult Hoffman before installing this 
equipment in conditions that may cause stresses beyond normal industrial conditions. 
 
The  Hoffman Purge/Pressurization Unit shall be installed and operated in accordance with 
relevant standards, such as IEC / EN 60079-14, NEC 500, NFPA 496 and any local codes of 
practice that are in force. 
 
For IEC / ATEX applications, references to the NFPA 496 within this instruction manual, should 
be replaced by the equivalent clause in IEC / EN 60079-2. 
 
For IEC / ATEX applications, the "Example calculations:" in section 1.1.4 within this instruction 
manual, should read: 
 

If the PE external dimensions indicate a volume of 0.5 m

3

 (17.7 Ft

3

) then, 

 

0.5 m3 (or 17.7 ft

3

) enclosure volume x volume changes = 12 minutes purge time 

0.225 m

3

/min (or 8 scfm purge flow rate 

 

Содержание PCFB1YZ

Страница 1: ...ication Sheet CF Y Z Purge Pressurization Unit 2 Application Suitability 3 Installation Operation and Maintenance for CF Units Section 0 Description and Principle of Operation Section 1 Installation o...

Страница 2: ...anada NFPA 496 UL E466718 Class I Div 1 Class I Div 2 Groups A B C D Groups A B C D For limitations and conditions of use refer to the applicable certificate at the back of this manual Supply Pressure...

Страница 3: ...t be fitted to the Pressurized Enclosure The following materials are used in the construction of Hoffman Purge Pressurization Units If substances that will adversely affect any of these materials are...

Страница 4: ...alibrated Outlet Orifices Where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply cap...

Страница 5: ...the PE Exception Power to Intrinsically Safe or other apparatus which is already suitable for the location need not be isolated by the Hoffman Purge Pressurization unit When utilizing Y Z Pressurizat...

Страница 6: ...the RLV and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor with a spare Check the condition of the air supply filter element Clean or replace it as necessary 3...

Страница 7: ...le cause 2 Excessive Pressurized Enclosure PE leakage Check around the PE when flow is taking place Any significant leakage must be cured Has a Leakage Test been done The total leakage should not exce...

Страница 8: ...Arrestor with circle clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air su...

Страница 9: ...Quick Installation Guide PCFF1YZ...

Страница 10: ...clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air supply to Control Unit 7...

Страница 11: ...Spark Arrestor Orifice Relief Valve Drawing...

Страница 12: ...Relief Valve Position Relief Valve Cutout Schematic for both PCFB1YZ and PCFF1YZ...

Страница 13: ...instructions and Article 504 of the NEC ANSI NFPA 70 3 For guidance on Installation see ANSI ISA RP12 6 Installation of IS Instrument Systems in Class I Hazardous Locations 4 Voc or Vt of associated a...

Страница 14: ......

Страница 15: ......

Страница 16: ...Hoffman Enclosures Inc 2100 Hoffman Way Anoka Minnesota 55303 1745 USA Phone 763 422 2211 www hoffmanonline com P N 89108870 Dwg 89109562 A...

Страница 17: ......

Отзывы: