TROUBLESHOOTING

The following network-related troubles can occur on the FireNET L@titude Fire Alarm Control Panel. See the
detailed descriptions below for explanations on each trouble message.

Trouble Message

Description

Network Communications Trouble

This event indicates there is no communication between this panel and its neighbor.
This could be caused by a configuration error (such as using the wrong baud rate), a
wiring error, or damage to the wires connecting the panel to its neighbor. If this trouble
occurs on one link on the panel, then the panel is still in communication with other
panels on the network. If this trouble occurs on both links on the panel, then the panel
is no longer in communication with other panels on the network.

Unexpected Network Node

This event indicates a panel has been detected on the network that is not in the
configuration. This is a configuration error, and should never occur once the network
has been properly configured.

Network Card Missing

This event indicates that the panel is configured for networking, but there is no
network card installed, or it is installed incorrectly. This trouble may also occur if the
network card processor fails.

Connection Error

This event indicates that the panel has failed to get a meaningful result for the link
impedance measurement. This may occur if stray leakage current enters the link
wiring from elsewhere, or if there is a component failure or missing jumper on the
network card. This event may also be shown when the network is disconnected or
when the NET OUT + wire is disconnected.

Network Panel Missing

This event indicates that another panel is configured but has not been found on the
network. This may occur if the missing panel is switched off or disconnected from the
network. This fault will also occur if there is no communication between a panel and
either of its neighbors on both links. In this case, the panel will show multiple
instances of this trouble; one for each other panel on the network.

Network Node Double Addressed

This event indicates that more than one panel on the network has the same node
number. This is a configuration error, and should never occur once the network has
been properly configured.

Full Short Circuit Trouble

This event indicates that a short circuit has been detected by the link impedance
measurement. This indicates a wiring error, or damage to the wires connecting the
panel to its neighbor.

Full Open Circuit Trouble

This event indicates that an open circuit has been detected by the link impedance
measurement. This indicates a wiring error, or damage to the wires connecting the
panel to its neighbor. The following two troubles are optional, and are not included in
the default firmware build.

Partial Short Circuit Trouble

This event indicates that the link impedance measurement has detected an
impedance below the normally expected range.

Partial Open Circuit Trouble

This event indicates that the link impedance measurement has detected an
impedance above the normally expected range.

Hochiki America Corporation

FireNET L@titude Network Module (S723) Information

Guide

Version 1.05 |   May 2019 |   MAN-1436HA

Page 13

Troubleshooting

Содержание FireNET L@titude S723

Страница 1: ...Version 1 05 May 2019 MAN 1436HA FireNET L titude Network Module S723 Information Guide...

Страница 2: ...4 Warranty Service 5 Advanced Replacements 5 Overview 6 Installation 7 Before You Begin 8 Placement 8 Network Connections 9 Testing 11 Troubleshooting 13 Specifications 14 Electrical 14 Operating Env...

Страница 3: ...ications not expressly approved by Hochiki America Corporation could void the user s authority to operate this equipment under the rules and regulations of the FCC Operation is subject to the followin...

Страница 4: ...mber is assigned when l Tech Support acknowledges a possible product failure l A product was damaged during shipping l An incorrect product was shipped l An order was placed using an incorrect part nu...

Страница 5: ...ll contractors who maintain an acceptable line of credit Initiate the advanced replacement process by requesting an RMA number from a Tech Support representative Advanced replacements can be shipped t...

Страница 6: ...used in conjunction with the Network Module provides tolerance against open and short circuit trouble conditions The L titude Network Module can be configured to operate in a bridge mode which enables...

Страница 7: ...from the panel q Connect the 40 conductor connector of the Network Module to the 40 conductor connector of the LCD Main Processor Board q Secure the Network Module to the LCD Main Processor Board wit...

Страница 8: ...on as quick and easy as possible Acquire the following item that is not included but may be required for installation l Ground Strap A ground strap is required for handling circuit boards The ground s...

Страница 9: ...s to NETWORK IN and NETWORK OUT terminals of the FireNET L titude Fire Alarm Control Panel s Main Back Board after installing the Network Module The following figure illustrates the typical network co...

Страница 10: ...minals must be connected together to prevent an OPEN CIRCUIT TROUBLE indication Bridge networking is supported for FireNET and FireNET Plus panels Advanced features are not available when using bridge...

Страница 11: ...Heartbeat Red Identifies functional status LED 2 Tx Comms Green A blinking green light indicates that the module is transmitting data LED 3 Rx Comms Green A blinking green light indicates that the mo...

Страница 12: ...ion present when flashing LED9 Full Duplex Yellow Full duplex on half duplex off LED 10 Ethernet Speed Red 10MHz off 100MHz on LED 12 Communication Green Communication present when flashing Hochiki Am...

Страница 13: ...also be shown when the network is disconnected or when the NET OUT wire is disconnected Network Panel Missing This event indicates that another panel is configured but has not been found on the networ...

Страница 14: ...work Vision Annunciator 21 30V DC L titude Fire Alarm Control Panel 24V DC Operating Environment Dry indoor use only Temperature Range 23oF 5oC 120oF 49oC Relative Humidity Up to 95 non condensing Hoc...

Страница 15: ...ss X 6 9 H Heartbeat 11 L LCD Main Processor Board 7 N Network 6 7 13 14 T Terminals 9 Trouble 6 10 Hochiki America Corporation FireNET L titude Network Module S723 Information Guide Version 1 05 May...

Отзывы: