Generator
Trouble, Symptom & Condition
Test or Inspection
Corrective Action
1.
Unbalanced output.
a. Loose connection in output
circuit.
Check all output connections,
Discolored connectors indicate a
loose connection. Tighten or
replace as required.
b. Open or short circuited
stator Phase.
Check stator windings in
accordance with Sect. 2-3,
Para. 4. Repair or replace as
required.
c. Defective connection in
output circuit.
Check plug and receptacle
connectors at aircraft. Tighten,
Repair or replace as required.
d. Unbalanced load.
Check aircraft 400-Hz
components.
OM-2040 / Operation and Maintenance Manual
90D20 / Generator Sets
February 28/94 Revised
Chapter 3-1
Page 25
Содержание 6921 Series
Страница 2: ...This page intentionally left blank ...
Страница 223: ......
Страница 224: ......
Страница 225: ......
Страница 226: ......
Страница 227: ......
Страница 228: ......
Страница 229: ......
Страница 230: ......
Страница 231: ......
Страница 232: ......
Страница 233: ......
Страница 234: ......
Страница 235: ......
Страница 236: ......
Страница 237: ......
Страница 238: ......
Страница 239: ......
Страница 240: ......
Страница 241: ......
Страница 242: ......
Страница 243: ......
Страница 244: ......
Страница 245: ......
Страница 246: ......
Страница 247: ......
Страница 248: ......
Страница 249: ......
Страница 250: ......
Страница 251: ......
Страница 252: ......
Страница 253: ......
Страница 254: ......
Страница 255: ......
Страница 256: ......
Страница 257: ......
Страница 258: ......
Страница 259: ......
Страница 260: ......