OM-2228 / Operation and Maintenance Manual
120CU20 / Series 500120 / 400 Hz. Generator Set
October 15, 2013
Chapter 2-3
Page 17
(3) Current Limiting / Soft Starting Control.
a
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 1500 A.
b
Press the “
DC OUTPUT
” push button to close the contactors to apply the load to the load
bank. Observe the ammeter, the current should stay below 1500 A.
c
Discontinue the power delivery.
(4) Over-Voltage Protection.
a
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
b
Adjust the voltage adjustment potentiometer on the TRB PC Board to range of 32-34 VDC.
c
With 7 to 9 seconds after the trip voltage is reached, the contactor will open and an over-
voltage fault will be indicated on the fault code meter, which will read “
70.28
”
d
Reset the voltage back to 28.5 VDC.
(5) Under-Voltage Protection.
a
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
b
Adjust the voltage adjustment potentiometer on the TRB PC Board to less than 20 VDC.
c
With 7 to 9 seconds after the trip voltage is reached, the contactor will open and an under-
voltage fault will be indicated on the fault code meter, which will read “
70.29
”
d
Reset the voltage back to 28.5 VDC.
(6) Overload Protection.
a
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 1500 A.
b
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
c
The contactor should open in 30 seconds. The fault code meter will read “
70.30
”
d
Discontinue power delivery and let the cables cool for 2-3 minutes.
e
Press the “
STARTNG CURRENT
” push button to activate the current limiting and set the limit
to 2000 A.
f
Press “
DC OUTPUT
” push button to close the DC output contactor. The blue “
DC OUTPUT
”
lamp will glow indicating that DC power is being delivered to the load bank.
Содержание 120CU20
Страница 2: ... ...
Страница 4: ... ...
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 208: ......
Страница 209: ......
Страница 210: ......
Страница 211: ......
Страница 212: ......
Страница 213: ......
Страница 214: ......
Страница 215: ......
Страница 216: ......
Страница 217: ......
Страница 218: ......
Страница 219: ......
Страница 220: ......
Страница 221: ......
Страница 222: ......
Страница 223: ......
Страница 224: ......
Страница 225: ......
Страница 226: ......
Страница 227: ......
Страница 228: ......
Страница 229: ......
Страница 230: ......
Страница 231: ......
Страница 232: ......
Страница 233: ......
Страница 234: ......
Страница 235: ......
Страница 236: ......
Страница 237: ......
Страница 238: ......