Basic Operation
11
Doc: HMSI-27-262, Rev: 2.10
Anybus X-gateway User Manaul
2.2 Status & Diagnostics
2.2.1 Status Word
Optionally, the gateway provides runtime status and diagnostics through the Status Word. This func-
tionality is disabled by default, but can be enabled separately for each network via the Gateway Config
Interface.
Status Word Contents:
• Gateway Cycle Counter
This 4-bit counter is incremented for each successful gateway cycle, i.e. each time data has been
successfully transferred between the network interfaces.
• General Error Counter
This 4-bit counter is incremented each time the throughput of the gateway exceeds 100 ms.
• Master Mode
1
These bits indicate the current operation mode of the on-board master to the other network
(these bits are not available on the master/scanner side).
The exact definition of these bits depend on the network in question. For further information,
consult the interface addendum for the on board master/scanner.
• Init
This bit indicates if the other network interface has been initialised as follows:
1: Other network interface successfully initialised.
0: Could not initialise other network interface.
• Run
This bit indicates the status of the data exchange on the other network as follows:
1: Other network is on line / running
0: Other network is not on line / not running
See also...
• See also “Controlling the Gateway from the Network” on page 13.
• See “Anybus Configuration Manager” on page 16.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Gateway Cycle Counter
General Error Counter
(reserved)
Master Mode
Init
Run
(MSB)
(LSB)
1. Master configurations only.