4.
Modbus Interface Specification
4.1
Modbus physical layer
INMBSMIT001I000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485
line. It performs 8N2 communication (8 data bits, no parity and 2 stop bit) with several
available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600
bps, 76800 bps and 115200 bps). It also supports 8N1 communication (8 data bits, no parity
and 1 stop bit).
4.2
Modbus Registers
All registers are type “1
6-
bit unsigned Holding Register”
and they use the standard
Modbus big
endian
notation.
4.2.1
Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/W
Description
0
1
R/W
AC unit On/Off
▪
0:Off
▪
1:On
1
2
R/W
AC unit Mode
1
▪
0:Auto
▪
1:Heat
▪
2:Dry
▪
3:Fan
▪
4:Cool
2
3
R/W
▪
0:Auto
▪
1:Low
▪
2:Mid-1
▪
3:Mid-2
▪
4:High
3
4
R/W
▪
0:Auto
▪
1:Horizontal
▪
2:Position-2
▪
3:Position-3
▪
4:Position-4
▪
Vertical
▪
Swing
4
5
R/W
1,2,3
▪
-32678 (Initialization value)
▪
16..32ºC (ºC/x10ºC)
▪
61..90ºF
5
6
R
▪
-32678 (Initialization value)
▪
10..38ºC (ºC/x10ºC)
▪
50..100ºF
1
Available values will depend on the AC unit mode. Check the AC unit model functions in its User
’s M
anual to know the possible values
for this register.
2
Magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (Default) or Fahrenheit. See section 4.2.3 for more
information
3
It is not possible turn to x10 the value shown in Fahrenheit.