HMS Networks Intesis EIA-485 Скачать руководство пользователя страница 11

Intesis

TM

 INMBSMIT001I000 

User’s Manual r22

 EN

 

 

 

 

  

 

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                11 / 20

 

4.2.3

 

Considerations on Temperature Registers 

 

 

AC unit temperature setpoint (R/W)

  

(register 4 

 in Protocol address / register 5 

 in PLC address): 

This is the adjustable temperature setpoint value that must be required by the User. This 
register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A 
Remote  Controller  connected  to  the  Mitsubishi  indoor  unit  will  report  the  same 
temperature  setpoint  value  as  this  register.  This  will  apply  when  no  AC  unit

s  external 

reference  temperature  is  provided  from  INMBSMIT001I000  (see  details  for  register 
22/23 below). 
 

 

AC unit temperature reference (R)

  

(register 5 

 in Protocol address / register 6 

 in PLC address):  

This register reports the temperature that is currently used by the Mitsubishi indoor unit 
as  the  reference  of  its  own  control  loop.  Depending  on  the  configuration  of  the  indoor 
unit, this value can be the temperature reported by the sensor on the return path of the 
Mitsubishi  indoor  unit  or  the  sensor  of  its  Remote  Controller.  It  is  a  read-only  register 
(Modbus functions 3 or 4). 

 

 

AC unit external temperature reference (Modbus) (R/W)

  

(register 22 

 in Protocol address / register 23 

 in PLC address):  

This  register  allows  us  to  provide  an  external  temperature’s  sensor  from  the  Modbus 

side. Mitsubishi indoor unit does not allow, on devices like INMBSMIT001I000, to provide 
directly  a  temperature  to  be  used  as  a  reference  of  the  control  loop  of  the  AC  indoor 
unit.  In  order  to  overcome  this  limitation  and  enable  the  usage  of  an  external 
temperature  sensor  (e.g.  from  Modbus  side),  INMBSMIT001I000  applies  the  following 

mechanism (only if “external temperature’s reference” is being used):

 

 

o

 

After a couple of values have been entered in the “AC unit external temperature’s 

reference”  (register  22/23)  and 

the 

“AC  unit  temperature  set  point”  (register 

4/5),  INMBSMIT001I000  calculates  the  corresponding  temperature

’s

  demand 

(e.g., 

if  a  “temperature  setpoint  (register  4/5)”  of 

22ºC

,  and  an  “external 

temperature reference (register 22/23)” of 

20ºC 

are entered, INMBSMIT001I000 

will assume that the user is demanding a 

+2ºC

 increase in temperature). 

 

o

 

By  knowing  at  any  time  the  ambient  temperature  currently  used  by  the  indoor 

unit to control its own operation (register 5/6),  INMBSMIT001I000 can calculate 
the required temperature setpoint needed to apply the decrease/increase on the 
real  temperature  and  reach  the  temperature  chosen  by  the  user  (following  the 
example  above,  if  INMBSMIT001I000 

reads  an  “ambient  temperature”  (register 

5/6)  of 

24ºC

  in  the  indoor  unit,  it  will  apply  a  final  setpoint  of 

24ºC  +  2ºC  = 

26ºC

). 

 

o

 

At  this  moment,  each  time  that  INMBSMIT001I000  detects  a  change  on  the 

ambient  temperature  reported  by  the  indoor  unit  (register  5/6),  it  will  also 
change  the  required  setpoint, in  order  to  keep  the  temperature  required  by  the 
user at any time. If we follow the last example, when INMBSMIT001I000 receives 
a  new  temperature´s  value  coming  from  the  indoor  unit  of 

25ºC

INMBSMIT001I000 will automatically adjust the temperature setpoint required of 
the AC indoor unit to 

25ºC + 2ºC = 27ºC

). 

 
 
 
 
 
 

Содержание Intesis EIA-485

Страница 1: ...Compatible with Domestic Mr Slim and City Multi lines commercialized by Mitsubishi Electric USER MANUAL Issue date 12 2017 r22 ENGLISH...

Страница 2: ...s information is subject to change without notice URL https www intesis com 2 20 Modbus RTU EIA 485 Interface for Mitsubishi Electric air conditioners Compatible with Domestic Mr Slim and City Multi l...

Страница 3: ...d are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables a...

Страница 4: ...Quick Start Guide 7 4 Modbus Interface Specification 8 4 1 Modbus physical layer 8 4 2 Modbus Registers 8 4 2 1 Control and status registers 8 4 2 2 Configuration Registers 10 4 2 3 Considerations on...

Страница 5: ...required Direct connection to Modbus RTU EIA 485 networks Up to 63 INMBSMIT001I000 devices can be connected on the same network INMBSMIT001I000 is a Modbus slave device Direct connection to the AC in...

Страница 6: ...nic circuit You can place the INMBSMIT001I000 inside or outside the AC indoor unit depending on your needs Remember that the INMBSMIT001I000 must also be connected to the Modbus RTU EIA 485 network Cl...

Страница 7: ...e and the AC indoor unit following the instructions of the diagram 4 Connect the EIA 485 bus to the interface s EIA485 connector 5 Close the AC indoor unit 6 Check the DIP Switch configuration of the...

Страница 8: ...ion 4 2 1 Control and status registers Register Address protocol address Register Address PLC address R W Description 0 1 R W AC unit On Off 0 Off 1 On 1 2 R W AC unit Mode 1 0 Auto 1 Heat 2 Dry 3 Fan...

Страница 9: ...other error present see the table at the end of this document 22 23 R W Indoor unit s ambient temperature from external sensor at Modbus side 1 2 3 6 32768 Initialization value No temperature is being...

Страница 10: ...ption 12 13 R W AC Model 13 14 R W Open Window switch off timeout 9 0 30 minutes Factory setting 30 minutes 14 15 R Modbus RTU baud rate 2400bps 4800bps 9600bps Default 19200bps 38400bps 57600bps 7680...

Страница 11: ...rovide directly a temperature to be used as a reference of the control loop of the AC indoor unit In order to overcome this limitation and enable the usage of an external temperature sensor e g from M...

Страница 12: ...tpoint s value shown by the Remote Controller or other Control System from Mitsubishi connected to the indoor unit may show a different value from the value shown in register 4 5 The User is not be ab...

Страница 13: ...rks S L U All rights reserved This information is subject to change without notice URL https www intesis com 13 20 Fahrenheit value Value in Modbus register is the temperature value in Fahrenheit i e...

Страница 14: ...e following locations The following tables apply to the interface s configuration through DIP switches SW1 AC indoor unit s features SW1 P1 4 Description Not used Default value Not used Not used Defau...

Страница 15: ...EIA 485 termination resistor Table 4 3 SW4 Temperature and termination resistor configuration SW4 P1 2 4 Description Temperature values in Modbus register are represented in degrees x1 Default value...

Страница 16: ...s Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 17: ...s ON 2s OFF Device correctly configured and working During normal operation LED OFF OFF continuously No Modbus Slave address configured During normal operation LED blinking 200ms ON 200ms OFF Communic...

Страница 18: ...tage signals For terminal solid wires or stranded wires twisted or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x...

Страница 19: ...subject to change without notice URL https www intesis com 19 20 6 List of supported AC Unit Types A list of Mitsubishi Electric indoor unit model s references compatible with INMBSMIT001I000 and its...

Страница 20: ...t of compressor 4220 Voltage anomaly 4230 Radiator panel temperature anomaly TH8 5101 Ambient temperature probe anomaly TH1 indoor unit 5102 Liquid probe anomaly TH2 5102 Cond Evap probe anomaly TH5 5...

Отзывы: