HCC-96RF-C(S) Series
HITROL CO.,LTD.
6
Installation
Precautions
for
Installation
- If more than one level switch is installed in a tank, the distance between each probe
shall be at least 300mm apart. (If the distance between probes is short, it may be
affected by the interconnection of the instrument, causing unstable operation.)
- For side mounting installation, an inactive rod shall be located at least 50mm inside of
tank, and it is recommended that the probe be tilted by 15 degrees to the horizontal
surface. (A foreign object between the nozzle and the probe may cause malfunction.)
- Protector shall have sufficient area to protect the sensor from incoming medium and
be installed at a distance that does not affect sensor operation.
- For side mounting installation, the cable entry shall be installed facing the ground to
maintain the waterproof function.
- When installing on the low level, carefully install the dead stock and material bridge.
- For outdoor installation, it is recommended to install the sun cover to avoid the effects
of temperature increases.
- In case of tank with stirrer, the probe shall be installed at a safe distance from the stirrer.
HCC-96RF-C(S) Series is generally used for high or low alarm with an installation on the side or
top of the tank and can be also applied to metallic or synthetic resin tank as there are no
restrictions on the material of the tank.
■ Side Mounting Installation
- If the content has the characteristics of creating an excess sediment layer, the
product shall be installed at an angle of about 45 degrees.
- If the content has a high density, a protector shall be installed at least 200mm
above from the probe in order to protect the probe.
■ Top Mounting Installation
- If the probe length is more than 1000mm, install a fixed bracket insulated at the bottom.
- Sensing probe shall be installed at least 500mm away from the side of the tank.