HCC-96RF-C
Setting Guide
RF Admittance Type Level Switch
Doc. no. : Rev0.0
Issued Date : 2020.11.18
APPENDIX Q
Страница 1: ...TORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 943 5600 www hitrol com INSTRUCTION MANUAL CAPACITANCE TYPE LEVEL SWITCH HCC 96...
Страница 2: ...Contents Overview 3 Characteristics 3 Operating Principle 3 Specifications 4 Product Composition 5 Installation 6 Precautions for Installation 6 Precautions for Attachment 7 Wiring 7 Precautions for...
Страница 3: ...ing from active sensing probe towards ground with reference RF signal when the medium is detecting Since all material has unique dielectric constant relative permittivity and conductance value that ar...
Страница 4: ...e Entry PBT 2 PF 1 2 F IP65 Std AL 2 PF 1 2 F IP66 Opt AL 2 PF 1 2 F IP66 AL 2 PF 1 2 F IP66 Amplifier Specification Module M 96RFC M 96RFS Microprocessor 16 Bit Microprocessor Oscillation Frequency 4...
Страница 5: ...Std NPT 1 PF 1 Others Flange ANSI JIS DIN Material SUS 316L Others Housing Connection Probe For HCC 96RF C Material PBT Material Aluminum Flat Type can be used in liquids but further verification is r...
Страница 6: ...roof function When installing on the low level carefully install the dead stock and material bridge For outdoor installation it is recommended to install the sun cover to avoid the effects of temperat...
Страница 7: ...maged while opening or closing the cover of product The grounding has an external and an internal grounding When connecting to an external ground the ground wire shall be 4 4mmSQ The internal groundin...
Страница 8: ...the product Precautions for Wiring Make sure to wire contacts correctly Wire and supply the power to the product after checking the specifications Incorrect power voltage may cause damage to the prod...
Страница 9: ...quest A S at our website or by contacting our headquarters Headquarters Factory Laboratory Contact Number ADDRESS HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea T E L 031 950 9700...
Страница 10: ...HCC 96RF C Setting Guide RF Admittance Type Level Switch Doc no Rev0 0 Issued Date 2020 11 18 APPENDIX Q...
Страница 11: ...stment 0 1s 3 RT Relay Return Time Adjustment Time Range 0 5s 1s 10s Adjustment 0 1s 4 Fail Safe Mode Relay Transformation Adjustment N C N O 5 DET Measurement Status LED OFF Red 6 RLY Relay Status LE...
Страница 12: ...r than the reference value No Function Method 1 Frequency Tuning To set the reference value while the DET LED is off adjust the TUN VR counter clockwise until the DET LED is on Fine tune TUN VR clockw...
Страница 13: ...clockwise until the DET LED is off No Function Method 1 Tuning Setting Status The TUN VR state according to the Tuning Setting is the most sensitive state Keep this status for sensitive use 2 Sensitiv...
Страница 14: ...y return time after undetecting the measurement No Function Method 1 DT Relay Delay Time Time Adjustment Range 0 5s 1s 10s Adjustment 0 1s No Function Method 1 RT Relay Return Time Time Adjustment Ran...
Страница 15: ...1 N C Relay Contact Out Default Status After detecting the measurement the contact point changes from N C to N O LED Status No Function Method 1 N O Relay Contact Out Opposite Status After detecting t...
Страница 16: ...sensor measurement status sensitivity setting value relay setting etc Monitoring Method Using PC Component PC USB Cable typical USB to Micro USB B UART Adaptor M 96RFC PC UART Component USB Cable M 9...
Страница 17: ...fer to Serial USB Terminal Install Guide USB Cable M 96RFC Smartphone UART Component M 96RFC Smartphone UART Execution Open App Home Screen Select UART Connection Enter Password Run Screen Enter exit...
Страница 18: ...HCC 96RF S Setting Guide RF Admittance Type Level Switch Doc no Rev0 0 Issued Date 2020 11 18 APPENDIX S...
Страница 19: ...djustment 0 1s 4 RT Relay Return Time Adjustment Time Range 0 5s 1s 10s Adjustment 0 1s 5 Fail Safe Mode Relay Transformation Adjustment N C N O 6 DET Measurement Status LED OFF Red 7 RLY Relay Status...
Страница 20: ...unction Method 1 Frequency Tuning Tune the cap trimmer for setting the default value Adjust clockwise until DET LED turns off 2 If the sensing LED does not turn off High capacitance in the tank Adjust...
Страница 21: ...he SEN VR state according to the Tuning Setting is the most sensitive state Keep this status for sensitive use 2 Sensitivity Adjustment You can adjust the sensitivity by adjusting SEN VR Sensitivity A...
Страница 22: ...ay Contact N C No Function Method 1 RT Relay Return Time Time Adjustment Range 0 5s 1s 10s Adjustment 0 1s No Function Method 1 N C Relay Contact Out Default Status After detecting the measurement the...
Страница 23: ...act status to Relay Contact N O No Function Method 1 N O Relay Contact Out Opposite Status After detecting the measurement the contact point changes from N O to N C LED Status Operating Status Accordi...
Страница 24: ...sensor measurement status sensitivity setting value relay setting etc Monitoring Method Using PC Component PC USB Cable typical USB to Micro USB B UART Adaptor USB Cable M 96RFS PC UART Component M 9...
Страница 25: ...Adaptor App Refer to Serial USB Terminal Install Guide USB Cable M 96RFS Smartphone UART Component Open App Home Screen Select UART Connection Enter Password Run Screen Enter PW and Fly command M 96RF...
Страница 26: ...Doc no Rev0 0 Issued Date 2020 04 29 Serial USB Terminal Serial USB Terminal Install Setting Guide Application Level Switch Level Transmitter APPENDIX H...
Страница 27: ...B Terminal App Search and Install a App that Serial USB terminal in the App Store Serial USB Terminal Setting Run The Serial USB Terminal Icon Four types of environments must be set up for normal oper...
Страница 28: ...minal Show connection message Show timestamps Setting Show connection message ON OFF Show timestamps ON OFF The size of the Terminal Font is the size set in the Smartphone Terminal Setting Terminal Fo...
Страница 29: ...no Rev0 0 Issued Date 2020 04 29 Receive Newline Setting Newline CR LF Carriage Return Line Feed Check Send Newline Setting Newline Auto same as Receive CR Select Newline Default Setting Complete Defa...
Страница 30: ...l echo Clear input on send Setting Local echo ON OFF Clear input on send OFF ON Local echo Setting Clear input on send Setting For detailed instructions refer to the manual of each product Select Clea...