TECHNICAL DATA
Serie MINI KRONO 2
801.1
1001.1
1201.1
1501.1
REFRIGERANT
Type
R-410A
Number of circuits
1
Global warming potential (GWP)
(4)
2088
COMPRESSOR
Type
SCROLL
Number of compressors
1
Number of power stages
1
Oil type
POE 160 SZ
Oil volume
L
3,3
3,6
Crankcase strength
W
65
FANS
Type
AXIAL
Number of fans
1
Rated air flow
m
3
/ h
16.700
19.500
Available static pressure
Pa
0
Diameter
mm
710
800
Absorbed power (by fan)
kW
1,5 / 1,12
2,06 / 1,33
Rated current (by fan)
A
3,0 / 1,7
3,8 / 2,3
Speed
r.p.m.
914 / 730
891 / 700
OUTDOOR HEAT EXCHANGER
Type
Aluminum fin coil and copper tubing
Quantity
1
1
1
1
Front surface of the exchanger
m
2
1,49
1,49
1,49
1,49
INDOOR HEAT EXCHANGER
Type
Water - Refrigerant
Quantity
1
Water volume
L
2,3
2,9
3,4
3,4
Anti-ice resistance
W
50
WATER CONNECTIONS
Type
SLOTTED
– Victaulic type
External diameter
(‘’)
1 1/2
ELECTRIC SPECIFICATIONS
Supply voltage
V / ~F / Hz
400 / 3+N / 50
Maximum intensity
A
21,7
23,1
26,9
33,1
Starting current (AC)
A
148
148
158,8
208,8
SOUND LEVEL
Sound power
dB(A)
84,3
84,4
83,5
85
Sound pressure (5m)
(5)
dB(A)
62,5
62,6
61,7
63,2
WEIGHT AND DIMENSIONS
Large
mm
1200
Width
mm
1050
High
mm
1470
Note:
(4)
GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO
2
, calculated in terms of 100-year warming potential.
(5)
Measurement conditions on the free field, directivity 2 and 1,5 meters above the floor.