![Hitecsa EKWXA 1001.1 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/hitecsa/ekwxa-1001-1/ekwxa-1001-1_installation-operation-and-maintenance-manual_2140039016.webp)
16
07.17 207443 Rev.105
EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
HYDRONIC KIT
TECHNICAL DATA
MINI KRONO 2
series
801.1
1001.1
1201.1
1501.1
HYDRONIC KIT
Expansion Vessel Volume
l
11
Deposit Inertia Volume
l
90
Available Pressure M H.K. Without Tank
kPa
27,9
24,4
28
41,4
Available Pressure M H.K. With Tank
kPa
28,1
24,6
28,3
41,8
Water Flow
m
3
/h
3,7
4,3
5,2
6,6
Connection Type
Slotted - Victaulic
Connection Diameter
(“)
1 ½
WATER PUMP OPTION
Power Supply
V/~/Hz
400/3/50
Number of Water Pump
1
Reserve Water Pump Option
NO
Maximum weight: Heat Pump + H.K. (full of
water)
kg
447
475
483
489
LOW PRESSURE PUMP
Model
120/3
Rated Power (per unit)
kW
0,55
Maximum Current (One Pump Operation)
A
1,6
Locked Rotor Current (One Pump)
A
9,4
Available Pressure M H.K. Without Tank
kPa
156,2
152,9
138,3
105
Available Pressure M H.K. With Tank
kPa
156,1
152,8
138
104,6
HIGH PRESSURE PUMP
Model
120/5
Rated Power (per unit)
kW
0,9
Maximum Current (One Pump Operation)
A
2,4
Locked Rotor Current (One Pump)
A
19,7
Available Pressure M H.K. Without Tank
kPa
247
242,4
225,5
188,7
Available Pressure M H.K. With Tank
kPa
246,9
242,3
225,3
188,3