12
07.17 207443 Rev.105
EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
INSTALLATION
SERVICE AREA
Be sure to respect the measures for a proper operation of the unit.
OPERATION
OPERATING LIMITS
TEMPERATURE
COLD
MINIMUM
MAXIMUM
Water Outlet
5ºC*
18ºC
Outdor Air (Dry Bulb)
10ºC**
46ºC
HEAT
MINIMUM
MAXIMUM
Water Outlet
25ºC
55ºC
Outdor Air (Wet Bulb)
-10ºC
22ºC***
* For lower temperatures it is necessary to use the water mixture with glycol.
** For lower temperatures use the optional condensing control.
*** For higher temperatures use the optional evaporation control.
OPERATING
LIMITS
801.1
1001.1
1201.1
1501.1
Minimum Water Flow
m
3
/h
2,4
2,8
3,3
4,2
Maximum Water Flow
m
3
/h
6,4
7,5
8,7
11,1
Minimum Volume of Water
l
54
63
73
93
1000 mm → Coil Side
1200 mm → Connections Side and Electrical Panel.