75
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
FA5
Frequency Arrival Type
5
–Set frequency
ON
When output to motor is at the set frequency,
during accel (
) and decel (
).
OFF When output to motor is OFF, or is not at a level of
the set frequency
OL2
Overload Advance
Notice Signal 2
ON
When output current is more than the set
threshold (
) for the overload signal
OFF When output current is less than the set threshold
for the deviation signal
ODc
Analog Voltage Input
Disconnect Detection
ON
When the [O] input value <
setting (signal
loss detected)
OFF When no signal loss is detected
OIDc
Analog Current input
Disconnect Detection
ON
When the [OI] input value <
setting (signal
loss detected)
OFF When no signal loss is detected
FBV
PID Second Stage
Output
ON
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (
)
OFF Transitions to OFF when the PID Process Variable
(PV) exceeds the PID High Limit (
), and
transitions to OFF when the inverter goes from
Run Mode to Stop Mode
NDc
Network Disconnect
Detection
ON
When the communications watchdog timer (period
specified by
) has time out
OFF When the communications watchdog timer is
satisfied by regular communications activity
LOG1
Logic Output Function 1 ON
When the Boolean operation specified by
has a logical
“1” result
OFF When the Boolean operation specified by
has a logical
“0” result
LOG2
Logic Output Function 2 ON
When the Boolean operation specified by
has a logical
“1” result
OFF When the Boolean operation specified by
has a logical
“0” result
LOG3
Logic Output Function 3 ON
When the Boolean operation specified by
has a logical
“1” result
OFF When the Boolean operation specified by
has a logical
“0” result
WAC
Capacitor Life Warning
Signal
ON
Lifetime of internal capacitor has expired.
OFF Lifetime of internal capacitor has not expired.
WAF
Cooling Fan Warning
Signal
ON
Lifetime of cooling fan has expired.
OFF Lifetime of cooling fan has not expired.
FR
Starting Contact Signal
ON
Either FW or RV command is given to the inverter
OFF No FW or RV command is given to the inverter, or
both are given to the inverter
OHF
Heat Sink Overheat
Warning
ON
Temperature of the heat sink exceeds a specified
value (
)
OFF Temperature of the heat sink does not exceed a
specified value (
)
LOC
Low load detection
ON
Motor current is less than the specified value
(
)
OFF Motor current is not less than the specified value
(
)