65
“b” Function
A
B
Defaults
Func.
Code
Name
Description
Initial data
Units
1st parameter of
Dual Monitor
Set any two "d" parameters in
and
,
then they can be monitored in
. The two
parameters are switched by up/down keys.
Set range:
~
001
2nd parameter of
Dual Monitor
002
Frequency set in
monitoring
Two option codes:
Freq. set disabled
Freq. set enabled
00
-
Automatic return
to the initial
display
10 min. after the last key operation, display
returns to the initial parameter set by
. Two
option codes:
Disable
Enable
00
-
Ex. operator com.
loss action
Five option codes:
Trip
Trip after deceleration to a stop
Ignore
Coasting (FRS)
Decelerates to a stop
02
-
Data Read/Write
select
Two option codes:
Read/Write enable
both Read, Write disable
00
-
Initialization
trigger
This is to perform initialization by parameter
input with
,
and
. Two option
codes:
Initialization disable
Perform initialization
00
-
Password
Settings A
0000(Invalid Password)
0001-FFFF(Password)
0000
-
Password
authentication A
0000-FFFF
0000
-
Password
Settings B
0000(Invalid Password)
0001-FFFF(Password)
0000
-
Password
authentication B
0000-FFFF
0000
-
Electronic thermal
subtraction
function selection
Four option codes:
OFF
Linear subtraction: pre-fixed ratio
Linear subtraction: ratio set in
Subtraction with first-order lag filter: ratio
set in
00
Thermal
subtraction time
This function is valid when
=
Range is 0.10 to 100000.00 s
Out of warranty when setting less than
initial value (600.00[s])
600.0
s
Thermal
subtraction time
constant
This function is valid when
=
Range is 0.10 to 100000.00 s
Out of warranty when setting less than
initial value (120.00[s])
120.00
s
Thermal
accumulation gain
Range is 1.0 to 200.0 %
Out of warranty when setting less than
initial value (100.0[%])
100.0
%
(NOTE 1) Invalid for the models without cooling fan.