68
“C” Function
A
B
Defaults
Func.
Code
Name
Description
Initial
data
Units
Electronic thermal warning
level
Set range is 0 to 100%
Setting 0 means disabled.
90.
%
Zero speed detection level
Set range is 0.00 to 100.0Hz
0.00
Hz
Heat sink overheat warning
Set range is 0. to 110.
C
100.
C
Communication speed
Eight option codes:
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
76,800 bps
115,200 bps
05
baud
Modbus address
Set the address of the inverter on the
network. Range is 1 to 247
1
Communication parity
Three option codes:
No parity
Even parity
Odd parity
00
Communication stop bit
Two option codes:
1 bit
2 bit
1
bit
Communication error select Selects inverter response to
communications error.
Five options:
Trip
Decelerate to a stop and trip
Disable
Free run stop (coasting)
Decelerates to a stop
02
Communication error
time-out
Sets the communications watchdog timer
period.
Range is 0.00 to 99.99 sec
0.0 = disabled
0.00
s
Communication wait time
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
0.
ms
O input span calibration
Scale factor between the external
frequency command on terminals L
–O
(voltage input) and the frequency output,
range is 0.0 to 200.0%
100.0
%
OI input span calibration
Scale factor between the external
frequency command on terminals L
–OI
(voltage input) and the frequency output,
range is 0.0 to 200.0%
100.0
%
Thermistor input (PTC)
span calibration
Scale factor of PTC input.
Range is 0.0 to 200.0%
100.0
%
Debug mode enable
Displays debug parameters.
Two option codes:
Disable
Enable
<Do not set>
(for factory use)
00
Communication selection
Modbus-RTU
EzCOM
EzCOM<administrator>
00