9
WL200 Inverter Specifications, continued
…
General Specifications
Item
Specifications
Protection structure
Note 4)
Open type (IP20
)
Con
tro
l
Control method
Line-to-line sinusoidal PWM method
Output frequency range Note 5)
0.10 to 400Hz
Frequency accuracy Note 6)
For maximum frequency, digital command ±0.01%, analog command
±0.2%
(
25±10
℃)
Frequency setting resolution
Digital setting: 0.01Hz Analog setting: Maximum frequency/1000
Voltage/Frequency characteristic
V/f characteristic (Constant torque, Reduced torque, Free V/f)
Rated overload current
120%/ 1 minute and 140%/ 12seconds
Acceleration/Deceleration time
0.00 to 3600 seconds (Linear, Curve optional setting).
Second acceleration/deceleration setting available.
Carrier frequency
2 to 10 kHz
DC braking
Operates when frequency became lower than deceleration frequency
by stop command, or when frequency became lower than setting
frequency at running, or by external input (level and time setting
available).
Protection function
Agaist overcurrent, overvoltage, undervoltage, electronic thermal,
abnormal temperature, earth fault overcurrent when powered on,
overload, over receive voltage, external trip, memory error, CPU error,
USP error, communication error, overvoltage suppression at
deceleration, momentary electric outage, emergency interrupt, etc.
In
p
u
t
s
ig
n
a
l
Frequency setting
Digital/Remote operator External Analog input signal: Variable
resistor/ DC0 to 10V / 4 to 20mA, Modbus communication
Operation/Stop command
Digital/Remote operator
External digital signal (3 wire input available), Modbus communication
Intelligent input
7 points (1, 2, 3/GS1, 4/GS2, 5/PTC, 6, 7/EB
)
Analog input
2 points (Voltage O terminal: 10bit/0 to 10V, Current OI terminal:
10bit/0 to 20mA)
O
u
tp
u
t
s
ig
n
a
l
Intelligent output
2 points (11/EDM, 12)
Intelligent relay output
1 point (1c contact point (AL0, AL1, AL2))
Analog output
1 point (AM terminal: 10bit/0 to 10V)
Pulse output
1 point (EO terminal: 32kHz
(
10V
)
)
Com
m
u
n
ic
a
ti
o
n
RS-422
RJ45 connector, Operator use
RS-485
Control circuit terminal stage, Modbus
USB
USB1.1, mini-B connector
O
th
e
r
fu
n
c
ti
o
n
s
AVR function, V/f characteristic switching, Upper/Lower limitter, 16 stage multi speed, Starting frequency
adjustment, Jogging operation, Carrier frequency adjustment, PID control, Frequency jump, Analog-in bias
adjustment, S-type acceleration.deceleratio, Electronic thermal chracteristic/Level adjustment, Retry
function, Torque boost function, Trip monitor, Soft lock function, Frequency conversion display, USP
function, Second control function, UP/DOWN, Overcurrent suppress function, etc.
G
e
n
e
ra
l
s
p
e
c
ifi
c
a
ti
o
n
s
Ambient temperature
-10 to 40
℃
(Derating is required) (Refer to the instruction manual)
Storage temperature
-20 to 65
℃
(Short time temperature during transportation)
Humidity
20 to 90% RH
Vibration
5.9m/s
2
(0.6G), 10 to 55Hz
Service space
Altitude lower than 1,000m, In-door (No corrosive gas, no dust)
Painting color
No painting,
[
Mold: Black(Munsell N1.5
)
]
Applicable standard
UL, CE, C-UL, C-tick, Safety Note 7)
Options
Noise filter, DC Reactor, AC Reactor, Remote operator, Connector
cable, Regenerative break unit, and Resistor, etc.
Note 1) Applicable motor is reference motor. When select motors, take notice so that rated current of motor
does not exceed over the inverter’s rated current.
Note 2) Output voltage decreases when power supply voltage is decreased.
Note 3) Control torque at capacitor feeding back is an average deceleration torque at the time of shortest
deceleration in motor unit (when stopped from 50Hz), not a continuous regenerated torque. Average
deceleration torque changes depending on motor loss. When operated exceeding over 50Hz, this
value is decreased.