– 73 –
2. Indoor fan does not operate (others are normal)
Can the fan be stopped by remote
control?
The microcomputer fan PWM
output (at pin ) is 1-5V.
Replace the microcomputer.
Replace the fan motor.
Replace the microcomputer.
Perform final operation check.
3. Air deflector does not move (others are normal)
Are pulse signals output at
microcomputer pins - when
auto swing is turned on in the fan
mode?
Replace the microcomputer.
Is a voltage over 15 or below 10V
being generated on the 12V line?
Replace IC111.
Yes
Yes
Yes
Yes
No
No
No
No
Check IC711. If it is normal,
replace the air deflector motor.
Perform final operation check.
24
15
18
RAS_AW_063-082e
11/17/06, 11:54 AM
73
Содержание Summit RAC-18YH6
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 18FH6 RAS 25FH6 INDOOR UNIT ...
Страница 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC 18YH6 RAC 25YH6 OUTDOOR UNIT ...
Страница 22: ... 20 CIRCUIT DIAGRAM MODEL RAS 18FH6 RAS 25FH6 RAS_AW_020 021_A2 2008 02 18 10 17 20 ...
Страница 23: ... 21 RAC 18YH6 RAC 25YH6 MODEL RAS_AW_020 021_A2 11 17 06 11 18 AM 21 ...
Страница 24: ... 22 RAS_AW_022_A3e 2008 02 19 16 33 22 ...
Страница 25: ... 23 Silent RAS_AW_023_A3e 2008 03 06 20 58 23 ...
Страница 27: ... 25 ...
Страница 28: ... 26 ...
Страница 30: ... 28 ...
Страница 31: ... 29 ...
Страница 47: ... 45 ...
Страница 48: ... 46 ...
Страница 50: ... 48 ...
Страница 51: ... 49 ...
Страница 52: ... 50 ...
Страница 54: ... 52 ...
Страница 71: ... 69 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18YH6 RAC 25YH6 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E10H2 ...
Страница 77: ... 75 ...
Страница 81: ... 79 ...
Страница 82: ... 80 ...
Страница 83: ... 81 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 18FH6 RAS 25FH6 ...
Страница 96: ...HITACHI AW NO 0024E RAS 18FH6 RAC 18YH6 RAS 25FH6 RAC 25YH6 ...