– 72 –
1. Power does not come on (no operation)
Is AC220-230V being generated
between terminals A and B on the
indoor unit terminal board?
Is AC220-230V being generated at
AC outlet?
Check AC outlet and breaker, and
repair any defective part.
Check the outdoor unit power circuit,
and repair any defective part.
Check according to the proper method
for checking the power circuit.
Check the reset circuit, and repair
any defective section.
Replace the microcomputer and
oscillator.
Is the control voltage being
generated normally?
12V line: 12V or 7V
5V line: 5V
Do the air deflectors perform initial
operation when the power supply is
turned on after off?
Check the power cable, power
switch, and terminal board, and
repair any defective part.
Check the indoor/outdoor unit
connection cable, and correct any
defective section (wrong connection,
incomplete insertion).
Is AC220-230V being generated
between terminals A and B on the
outdoor unit terminal board?
Is DC35V or 20V being generated
between terminals C and D on the
indoor unit terminal board?
Is the microcomputer reset input
(pin
7
) "Hi"?
Is the microcomputer clock signal
10MHz at pins
0
and
A
being
generated normally?
Is DC35V is being generated between
terminals C and D on the outdoor unit
terminal board?
Are C and D connection cables
reversed?
Connect the cables correctly.
Check the wireless light receiving unit.
Replace the control P.W.B.
Perform final operation check.
: When not in operation, the unit will enter into a low-power standby state, possibly causing a voltage drop to the 12V and 35V lines
as shown below.
25V - 20V
12V - 7V
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
1
1
CHECKING THE INDOOR UNIT ELECTRICAL PARTS
RAS_AW_063-082e
11/17/06, 11:54 AM
72
Содержание Summit RAC-18YH6
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 18FH6 RAS 25FH6 INDOOR UNIT ...
Страница 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC 18YH6 RAC 25YH6 OUTDOOR UNIT ...
Страница 22: ... 20 CIRCUIT DIAGRAM MODEL RAS 18FH6 RAS 25FH6 RAS_AW_020 021_A2 2008 02 18 10 17 20 ...
Страница 23: ... 21 RAC 18YH6 RAC 25YH6 MODEL RAS_AW_020 021_A2 11 17 06 11 18 AM 21 ...
Страница 24: ... 22 RAS_AW_022_A3e 2008 02 19 16 33 22 ...
Страница 25: ... 23 Silent RAS_AW_023_A3e 2008 03 06 20 58 23 ...
Страница 27: ... 25 ...
Страница 28: ... 26 ...
Страница 30: ... 28 ...
Страница 31: ... 29 ...
Страница 47: ... 45 ...
Страница 48: ... 46 ...
Страница 50: ... 48 ...
Страница 51: ... 49 ...
Страница 52: ... 50 ...
Страница 54: ... 52 ...
Страница 71: ... 69 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18YH6 RAC 25YH6 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E10H2 ...
Страница 77: ... 75 ...
Страница 81: ... 79 ...
Страница 82: ... 80 ...
Страница 83: ... 81 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 18FH6 RAS 25FH6 ...
Страница 96: ...HITACHI AW NO 0024E RAS 18FH6 RAC 18YH6 RAS 25FH6 RAC 25YH6 ...