– 68 –
No.
Blinking of Timer lamp
Reason for indication
Possible cause
Reversing valve defective
When the indoor heat exchanger
temperature is too low in the
heating mode or it is too high in the
cooling mode.
Outdoor unit is under forced
operation
Outdoor unit electrical components
defetive
When the outdoor unit is in forced
operation or balancing operation
after forced operation
Indoor/outdoor interface defective
When the interface signal from the
outdoor
When the same error mode is detected
8 times within 30 minutes from outdoor
unit electrical components.
(However, when error is detected 8
times within two hours only for outdoor
thermistor.)
unit is interrupted.
Room thermistor or heat exchanger
thermistor is faulty
When room thermistor or heat
exchanger thermistor is opened
circuit or short circuit.
Over-current detection at the DC fan
motor
when over-current is detected at the
DC fan motor of the indoor unit.
IC401 or IC402 data reading error
When data read from IC401 or
IC402 is incorrect.
(1) Reversing valve defective
(2) Heat exchanger thermistor
disconnected
(only in the heating mode)
(Note)
The malfunction mode is entered the
3rd time this abnormal indication
appears (read every 3 minutes).
Electrical parts in the outdoor unit
(1) Indoor interface circuit
(2) Outdoor
Outdoor unit electrical components
(For details, operate again using
remote comtroller and check from
self-diagnosis display of outdoor
unit.)
interface circuit
(1) Room thermistor
(2) Heat exchanger thermistor
(1) Indoor fan locked
(2) Indoor fan motor
IC401 or IC402 abnormal
1
2
3
4
5
6
7
(
Lights for 0.35 sec. at interval of 0.35 sec.)
10 times
3 times
1 time
2 times
13 times
2 sec.
2 sec.
2 sec.
2 sec.
2 sec.
1
9 times
2 sec.
(3) Indoor control P.W.B.
4 times
2 sec.
<Cautions>
(1)
If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2)
If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit.
(3)
To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Model RAS-18FH6, RAS-25FH6
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301
blink.
SELF-DIAGNOSIS LIGHTING MODE
Model: RAS-18FH6, RAS-25FH6
RAS_AW_063-082e
2008.1.28, 16:06
68
Содержание Summit RAC-18YH6
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 18FH6 RAS 25FH6 INDOOR UNIT ...
Страница 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC 18YH6 RAC 25YH6 OUTDOOR UNIT ...
Страница 22: ... 20 CIRCUIT DIAGRAM MODEL RAS 18FH6 RAS 25FH6 RAS_AW_020 021_A2 2008 02 18 10 17 20 ...
Страница 23: ... 21 RAC 18YH6 RAC 25YH6 MODEL RAS_AW_020 021_A2 11 17 06 11 18 AM 21 ...
Страница 24: ... 22 RAS_AW_022_A3e 2008 02 19 16 33 22 ...
Страница 25: ... 23 Silent RAS_AW_023_A3e 2008 03 06 20 58 23 ...
Страница 27: ... 25 ...
Страница 28: ... 26 ...
Страница 30: ... 28 ...
Страница 31: ... 29 ...
Страница 47: ... 45 ...
Страница 48: ... 46 ...
Страница 50: ... 48 ...
Страница 51: ... 49 ...
Страница 52: ... 50 ...
Страница 54: ... 52 ...
Страница 71: ... 69 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18YH6 RAC 25YH6 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E10H2 ...
Страница 77: ... 75 ...
Страница 81: ... 79 ...
Страница 82: ... 80 ...
Страница 83: ... 81 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS 18FH6 RAS 25FH6 ...
Страница 96: ...HITACHI AW NO 0024E RAS 18FH6 RAC 18YH6 RAS 25FH6 RAC 25YH6 ...