1- 5
Function mode
Code
Function name
SJ300 Setting range
Initial data
-FE/-FU/-F
Note
b012
Electronic thermal level
0.2*constant current-1.20*constant current(A)
Rated
Current of
inverter
b212
Electronic thermal level
(2
nd
motor)
0.2*constant current-1.20*constant current(A)
Rated
Current of
Inverter
b312
Electronic thermal level
(3
rd
motor)
0.2*constant current-1.20*constant current(A)
Rated
current of
inverter
b013
1
s t
electronic thermal
characteristic selection
00(reduced characteristic)/ 01(constant torque characteristic)/
02(free setting)
01/01/00
b213
2
nd
electronic thermal
characteristic selection
00(reduced characteristic)/ 01(constant torque characteristic)/
02(free setting)
01/01/00
b313
3
rd
electronic thermal
characteristic selection
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
01/01/00
b015
Free electronic thermal
frequency 1
0.-400.(Hz)
0.
b016
Free electronic thermal
current 1
0.0-1000.(A)
0.0
b017
Free electronic thermal
frequency 2
0.-400.(Hz)
0.
b018
Free electronic thermal
current 2
0.0-1000. (A)
0.0
b019
Free electronic thermal
frequency 3
0.-400.(Hz)
0.
b020
Free electronic thermal
current 3
0.0-1000.(A)
0.0
b021
Overload restriction selection
00(invalid)/01(enabled on acceleration / constant speed)/
02(enabled on constant speed)/03(enabled on acceleration / constant
speed (speed increasing at regenerating mode))
01
b022
Overload restriction level
0.50* rated current-2.00* rated current(A) <-1.80*ratede current(A)>
Rated current
of Inverter
x 1.50
b023
Overload restriction limit
constant
0.10-30.00(s)
1.00
b024
Overload restriction 2
selection
00(invalid)/01(enabled on acceleration / constant speed)/
02(enabled on constant speed)/03(enabled on acceleration / constant
speed (speed increasing at regenerating mode))
01
b025
Overload restriction level 2
0.50*rated current-2.00*rated current(A) <-1.80*rated current(A)>
Rated current
of inverter
x1.50
b026
Overload restriction constant
2
0.10-30.00(s)
1.00
b031
Software lock mode selection
00(impossible to change the data except this item when SFT terminal is
ON)/01(impossible to change the data except setting frequency item
when SFT terminal is ON)/02(impossible to change the data except this
item)/
03(impossible to change the data except setting frequency item)/
10(possible to change data on operating)
01
b100
Free V/f frequency 1
0.- Free V/f frequency2(Hz)
0.
b101
Free V/f voltage 1
0.-800.0(V)
0.0
b102
Free V/f frequency 2
0.- Free V/f frequency3(Hz)
0.
b103
Free V/f voltage 2
0.-800.0(V)
0.0
b104
Free V/f frequency 3
0.- Free V/f frequency4(Hz)
0.
b105
Free V/f voltage 3
0.-800.0(V)
0.0
b106
Free V/f frequency 4
0.- Free V/f frequency5(Hz)
0.
b107
Free V/f voltage 4
0.-800.0(V)
0.0
b108
Free V/f frequency 5
0.- Free V/f frequency6(Hz)
0.
b109
Free V/f voltage 5
0.-800.0(V)
0.0
b110
Free V/f frequency 6
0.- Free V/f frequency7(Hz)
0.
b111
Free V/f voltage 6
0.-800.0(V)
0.0
b112
Free V/f frequency 7
0.-400.(Hz)
0.
b113
Free V/f voltage 7
0.-800.0(V)
0.0
C001
Intelligent input 1 setting
18
C002
Intelligent input 2 setting
16
C003
Intelligent input 3 setting
06
C004
Intelligent input 4 setting
11
C005
Intelligent input 5 setting
09
C006
Intelligent input 6 setting
03/13/03
C007
Intelligent input 7 setting
02
C008
Intelligent input 8 setting
01/(RV:Reverse is valid)/02(CF1:Multi-speed1)/ 03(CF2:Multi-speed2)/
04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 06(JG:Jogging)/
07( DB:External DC braking)/ 08(SET:2
nd
control)/
09(2CH:two-stage adjustable speed)/ 11( FRS:Free-run)/ 12( EXT:External trip)/
13( USP:Unattended start protection)/ 14(CS:commercial change)/
15(SFT:software lock)/ 16(AT:Analog input voltage/current select)/
17(SET3:3
rd
control)/ 18(RS:Reset inverter)/ 20(STA:3wire run)/
21(STP:3wire keep)/ 22(F/R:3wire forward/reverse)/
23(PID:PID selection valid/invalid)/ 24(PIDC:PID integrating reset)/
26( CAS:Control gain switch function)/ 27( UP:Remote control UP function)/
28( DWN:Remote control DOWN function)/29( UDC:Remote control data clear)/
31( OPE:Operating by operator select)/ 32(SF1:Multi-speed bit1)/
33(SF2:Multi-speed bit2)/ 34(SF3:Multi-speed bit3)/ 35(SF4:Multi-speed bit4)/
36(SF5:Multi speed bit5)/ 37(SF6:Multi-speed bit6)/ 38(SF7:Multi-speed bit7)/
39( OLR:Overload restriction change) / 40(TL:Torque limit select)/
41(TRQ1:Torque limit switch 1)/ 42(TRQ2:Torque limit switch 2)/
43((PPI:P/PI switch)/ 44(BOK:Braking comformation)/ 45( ORT:Orientation)/
46(LAC:LAD cancel)/ 47(PCLR:Position error clear)/
48(STAT:Permission of pulse train)/ no(NO:No assign)
01
(Note) < > indicate the setting range of 75 to 150kW
Electronic thermal
Free V/f setting
Intelligent input terminal setting
Overload limit
Содержание SJ300 Series
Страница 39: ...Internal block diagram ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......