1- 13
Function Mode
Code
Function name
L300P Setting range
Initial data
-FE/-FU/-FR
N o t e
b021
Overload restriction
selection
00(invalid)/01(enabled on acceleration / constant speed)/02(enabled
on constant speed)
01
b022
Overload restriction level
0.50* rated current-1.50* rated current(A)
Rated
current of
inverter
x 1.20
b023
Overload restriction limit
constant
0.10-30.00(s)
1.00
b024
Overload restriction 2
selection
00(invalid)/01(valid on acceleration / constant speed)/02(valid on
constant speed)
01
b025
Overload restriction level 2
0.50*rated current-1.50*rated current(A)
Rated
current of
inverter
x1.20
b026
Overload restriction
constant 2
0.10-30.00(s)
1.00
b031
Software lock mode
selection
00(impossible to change the data except this item when SFT terminal
is ON)/01(impossible to change the data except setting frequency
item when SFT terminal is ON)/02(impossible to change the data
except this item)/03(impossible to change the data except setting
frequency item)/10(possible to change data on operating)
01
b100
Free V/f frequency 1
0.- Free V/f frequency2(Hz)
0.
b101
Free V/f voltage 1
0.-800.0(V)
0.0
b102
Free V/f frequency 2
0.- Free V/f frequency3(Hz)
0.
b103
Free V/f voltage 2
0.-800.0(V)
0.0
b104
Free V/f frequency 3
0.- Free V/f frequency4(Hz)
0.
b105
Free V/f voltage 3
0.-800.0(V)
0.0
b106
Free V/f frequency 4
0.- Free V/f frequency5(Hz)
0.
b107
Free V/f voltage 4
0.-800.0(V)
0.0
b108
Free V/f frequency 5
0.- Free V/f frequency6(Hz)
0.
b109
Free V/f voltage 5
0.-800.0(V)
0.0
b110
Free V/f frequency 6
0.- Free V/f frequency7(Hz)
0.
b111
Free V/f voltage 6
0.-800.0(V)
0.0
b112
Free V/f frequency 7
0.-400.(Hz)
0.
b113
Free V/f voltage 7
0.-800.0(V)
0.0
C001
Intelligent input 1 setting
18
C002
Intelligent input 2 setting
16
C003
Intelligent input 3 setting
03/13/03
C004
Intelligent input 4 setting
02
C005
Intelligent input 5 setting
0 1 / (RV:Reverse is valid)/02(CF1:Multi-speed1)/ 0 3 ( C F 2 : M u l t i - s p e e d 2 ) /
04(CF3:Multi-speed3)/ 05(CF4:Multi-speed4)/ 0 6 (JG:Jogging)/
07(DB:External DC braking)/08(SET:2
nd
control)/
09(2CH:two-stage adjustable speed)/11(FRS:Free-run)/
12(E X T : E x t e r n a l t r i p ) / 1 3 ( USP:Unattended start protection)/
14(CS:commercial change)/15(SFT:software lock)/
16(AT:Analog input voltage/current select)/18(RS:Reset inverter)/
20(STA:3wire run)/ 21(STP:3wire keep)/22(F/R:3wire forward/reverse)/
23(PID:PID selection valid/invalid)/24(PIDC:PID integrating reset)/
2 7 ( U P : R e m o t e c o n t r o l U P f u n c t i o n ) /
28(DWN:Remote control DOWN function)/
29(U D C : R e m o t e c o n t r o l d a t a c l e a r ) / 3 1 ( OPE:Force operate o p e ) /
32(SF1:Multi-speed bit1)/
33(SF2:Multi-speed bit2)/34(SF3:Multi-speed bit3)/
35(SF4:Multi-speed bit4)/36(SF5:Multi speed bit5)/
37(SF6:Multi-speed bit6)/38(SF7:Multi-speed bit7)/
39(OLR:Overload restriction change)/no(NO:No assign)
01
C011
Intelligent input1 a/b
(NO/NC) selection
00(NO)/01(NC)
00
C012
Intelligent input2 a/b
(NO/NC) selection
00(NO)/01(NC)
00
C013
Intelligent input3 a/b
(NO/NC) selection
00(NO)/01(NC)
00/01/00
C014
Intelligent input4 a/b
(NO/NC) selection
00(NO)/01(NC)
00
C015
Intelligent input5 a/b
(NO/NC) selection
00(NO)/01(NC)
00
C019
Input FW a/b (NO/NC)
Selection
00(NO)/01(NC)
00
C021
Intelligent output 11 setting
01
C022
Intelligent output 12 setting
00
C026
Alarm relay output
00( RUN:running)/01(FA1:Frequency arrivaltype1 signal)/
02(FA2:frequency arrival type2 signal)/03(OL:Overload advance
notice signal)/04(OD:Output deviation for PID control)/05(AL:Alarm
signal)/06(FA3:Only setting frequency)/08( IP:On instantaneous stop/
09( UV:Under voltage)/11(RNT:RUN time over)/12(ONT:ON time
over)/
13( THM:thermal caution)
05
C027
FM selection
00(Output frequency)/01(Output current) /
03(Digital output frequency)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00
C028
AM selection
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(thermal load rate)/07(LAD frequency)
00
C029
AMI selection
00(Output frequency)/01(Output current)/04(Output voltage)/
05(Input electric power)/06(Thermal load rate)/07(LAD frequency)
00
C031
Intelligent output 11 a/b
00(NO)/01(NC)
00
C032
Intelligent output 12 a/b
00(NO)/01(NC)
00
C036
Alarm relay output a/b
00(NO)/01(NC)
01
C040
Overload advance notice
signal output mode
00(On accel. And decel, constant speed)/01(Only constant speed)
01
C041
Overload advance notice
level
0.0-2.0*rated current(A)
Inverter
rated current
C042
Frequency arrival setting
for acceleration.
0.00-99.99/100.0-400.0(Hz)
0.00
C043
Arrival frequency setting for
deceleration.
0.00-99.99/100.0-400.0(Hz)
0.00
C044
PID deviation setting level
0.0-100.0(%)
3.0
Overload limit
Lock
Free V/f setting
Intelligent input terminal setting
Intelligent output terminal setting
Output terminal state setting,
Output level setting
Input terminal setting
intelligent
Содержание SJ300 Series
Страница 39: ...Internal block diagram ...
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......