Inverse characteristic
M12388-1 v24
Table 215. ANSI Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
P
A
t
B
k
I
=
+
⋅
−
EQUATION1249-SMALL V3 EN-US
Reset characteristic:
( )
2
1
=
×
-
tr
t
k
I
EQUATION1250-SMALL V1 EN-US
I = I
measured
/I
set
0.05 ≤ k ≤ 999.00
1.5 x I
set
≤ I ≤ 20 x I
set
ANSI/IEEE C37.112 ,
±2.0% or ±40 ms
whichever is greater
ANSI Extremely Inverse
A=28.2, B=0.1217, P=2.0 , tr=29.1
ANSI Very inverse
A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse
A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse
A=0.0515, B=0.1140, P=0.02, tr=4.85
Long Time Extremely Inverse
A=64.07, B=0.250, P=2.0, tr=30
Long Time Very Inverse
A=28.55, B=0.712, P=2.0, tr=13.46
Long Time Inverse
A=0.086, B=0.185, P=0.02, tr=4.6
Table 216. ANSI Inverse time characteristics for Line differential protection
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
P
A
t
B
k
I
=
+
⋅
−
EQUATION1249-SMALL V3 EN-US
Reset characteristic:
( )
2
1
=
×
-
tr
t
k
I
EQUATION1250-SMALL V1 EN-US
I = I
measured
/I
set
0.05 ≤ k ≤ 1.10
ANSI/IEEE C37.112 ,
±5.0% or ±40 ms
whichever is greater
ANSI Extremely Inverse
A=28.2, B=0.1217, P=2.0 , tr=29.1
ANSI Very inverse
A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse
A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse
A=0.0515, B=0.1140, P=0.02, tr=4.85
Long Time Extremely Inverse
A=64.07, B=0.250, P=2.0, tr=30
Long Time Very Inverse
A=28.55, B=0.712, P=2.0, tr=13.46
Long Time Inverse
A=0.086, B=0.185, P=0.02, tr=4.6
Line differential protection RED670
1MRK 505 379-BEN R
Version 2.2
Hitachi Energy
157
© 2017 - 2022 Hitachi Energy. All rights reserved