Logic
M12380-1 v15
Table 110. Tripping logic common 3-phase output SMPPTRC
Function
Range or value
Accuracy
Trip action,
Program
3 phase, 1ph/2ph, 1ph/2ph/3ph
-
Minimum trip pulse
length ,
tTripMin
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
3-pole trip delay,
tWaitForPHS
(0.020-0.500) s
±0.2% or ±15 ms whichever is greater
Evolving fault delay
,
tEvolvingFault
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1
Table 111. Number of SMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
SMAGAPC
12
-
-
Table 112. Number of STARTCOMB instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
STARTCOMB
32
-
-
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3
Table 113. Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TMAGAPC
6
6
-
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2
Table 114. Number of ALMCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
ALMCALH
-
-
5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2
Table 115. Number of WRNCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
WRNCALH
-
-
5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2
Table 116. Number of INDCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
INDCALH
-
5
-
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3
Table 117. Number of AND instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
AND
60
60
160