![Hitachi RCI-1.5TNE1NH Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/hitachi/rci-1-5tne1nh/rci-1-5tne1nh_installation-and-maintenance-manual_2139380027.webp)
Installation and Maintenance
23
(
1
)
Prepare a polyvinyl chloride pipe with a 32mm outer diameter (3.0~6.5).
For Model1.5/2.0 : a
≤
300
,
b
≤
500
,
c
≤
50
For Model 3.0~6.5: a
≤
300
,
b
≤
850
,
c
≤
50,a+b+c
≤
1100
Prepare a polyvinyl chloride pipe with a 21mm inside diameter (1.5/2.0).
(
2
)
Fasten the tubing to drain hose with the adhesive agent and factory
-
supplied clamp
.
The drain piping
must be performed with a down-slope pitch of 1/25 to 1/100.
*
The
total
length
of
a
+
b
+
c
:
*
In case of lifting the drain pipe at outlet part
,
perform the drain piping work as shown in the
above
figure
.
(
3
)
Insulate the drain pipe after connecting the drain hose
.
Hose Band
(Accessory)
Hose Band
(Accessory)
Drain House
(Accessory)
Drain House
(Accessory)
1/25 to 1/100
Down-Slope
Vinyl Chloride
(Field Supplied)
Drain Pipe
Connection
850mm
Max.
Unit
Upward Slope
Rising part
Drain Pipe
Connection
1/25 to 1/100 Down-Slope
Common Drain Piping
This drain pipe shall be
separating from other pipes
Hose Band (Accessory)
Packing (5Tx270x270)
(Accessory)
Содержание RCI-1.5TNE1NH