Installation
(
3
.
0
~
6
.
5HP
)
3
.
3
.
2
Mounting
Position
of
the
Indoor
Unit
Installation and Maintenance
15
Model
3.0/4.0
5.0/6.0/6.5
Fig
.
3
.
5
Mounting
Position
3
.
3
.
1
Opening
of
False
Ceiling
and
Suspension
Bolts
(
1
)
Determine the final location
of the indoor unit paying careful attention
and direction of installation
to
the
space
for
the
piping
,
wiring
and
maintenance
.
Pattern board
for installation is printed on the packing. Cut off the pattern for opening
the false
ceiling and installation suspension bolts.
(
2
)
Cut
out
the
area
for
the
indoor
unit
in
the
false
ceiling
and
install
suspension
bolts, as
shown
in
Fig
.
3
.
3
.
Fig
.
3
.
3
Opening of False Ceiling and Suspension Bolts
(
3
)
Check to ensure that the ceiling is horizontally level, otherwise drainage can not flow
.
(
4
)
Strengthen the opening parts of the false ceiling
.
(
5
)
Mount suspension bolts, as shown in Fig
.
3
.
4
.
Fig
.
3
.
4
Mounting Suspension Bolts
150 to 160mm
I
Beam
Suspension
Boit
(
W3
/
8
or
M10
)
For Concrete Slab
For steel Beam
Insert
(100 to 150kg)
Concrete
Anchor Bolt
(W3/8 or M10)
(mm)
(4-Suspension Bolts)
M10 or W3/8 (Field-Spplied)
W-Nut (Field Supplied)
Washer (Accessary)
Surface of Ceiling
a
* indicates the dimension between
lower face of indoor unit and
surface of ceiling.
Liquid Pipe Connection
Gas Pipe Connection
(mm)
Drain Pipe Connection
Wiring Hole (
ø
32.5 Hole)
1
18 ( Drain Pipe)
(for Spare)
Wiring Hole (30x30)
(for Cable)
127 (Liquid Pipe Connection)
102 (Gas Pipe Connection)
Fig
.
3
.
6 Indoor Unit and Air Panel
248
298