4-32
OPTIONAL FUNCTION
(4.3 Outdoor Unit)
4.3.10 Night Shift (Low Sound) Operation
By changing No.2 of the dip switch, DSW5, the night shift (low sound) operation can be set.
In case of the night shift operation, the cooling capacity is decreased down to 60%. The night shift
operation shall be applied only in case that the cooling capacity has the margin to be allowed for the
capacity decrease and the low sound operation is required especially in the nighttime.
(1) Outdoor Fan
NOTE:
The maximum rotation is always 100% (rotation ratio) for the standard unit.
(No limitation of the outdoor temperature)
(2) Frequency Range
Converted Frequency of Constant Speed Compressor
NOTE:
The maximum frequency for the 8 to 30HP outdoor unit is indicated as;
Inverter Fre Converted Frequency of Constant Speed Compressor.
Outdoor Unit
Capacity (HP)
Minimum
Frequency
Maximum
Frequency
When
5
95Hz
Except for the Conditions Below
Night Shift
8
165Hz
is not Set
10
177Hz
16
255Hz
20
325Hz
24
385Hz
30
465Hz
When
5
50Hz
(1) Night Shift Operation
Night Shift
8
100Hz
(2) Cooling Operation
is Set
10
114Hz
(3) Outdoor Fan: Below 70%
16
140Hz
20
176Hz
24
211Hz
30
255Hz
50Hz
60Hz
50Hz
60Hz
62Hz
74Hz
70 x 2Hz
84 x 2Hz
70 x 3Hz
84 x 3Hz
70+100 x 2Hz
84+120 x 2Hz
70+140 x 2Hz
84+168 x 2Hz
24
30
30Hz
30Hz
16
20
Conditions
8
Power Supply Frequency
10
Outdoor Unit Capacity
(HP)