1-5
TROUBLESHOOTING
1 2 3 4 5 6
ON
OFF
DSW2
1 2
ON
OFF
DSW5
Factory Setting Position
(Dip Switch)
DSW2
PCB2
DSW5
b. Setting of Dip Switches
The dip switches are set before shipment and no setting in the field is required. These are utilized
for the self-diagnosis of PCB.
(3) CH Unit (For FX Series Only)
Before setting dip switches, firstly turn OFF power source and set the position of the dip switches.
If the dip switches are set without turning OFF the power source, the switches can not function.
The “
■
” mark indicates position of dip switches. The figures below show the setting before
shipment.
a. Position of Dip Switches
The PCB2 in the electrical box of CH unit is equipped with 2 types of dip switches (DSW2, DSW5),
as shown in the figure below.
NOTE
1.1.2 Checking of Electrical Wiring
Check to ensure that the terminal for power source wiring (terminals “L1” to “L1” and “N” to “N” of
each terminal board: AC380-415V, terminals “R” to “R” and “T” to “T” of each terminal board:
AC220V) and intermediate wiring (Operating Line: terminals “1” to “1” and “2” to “2” of each terminal
board: DC5V) between the indoor unit and the outdoor unit coincide correctly, as figure below. If not,
some component will be damaged.
Check to ensure that the twist pair cable with shield (
≥
0.75mm2) are used for intermediate wiring to
protect noise obstacle at total length of less than 1000m and size complied with local code.
Check to ensure that the wirings and the breakers are chosen correctly, as shown in Table 1.1. and
1.2.
All the field wiring and equipment must comply with local code.