4-18
OPTIONAL FUNCTION
(4.2 Indoor Unit)
Table 4.4 Specifications on Required Components
NOTE:
Make the wires CN3 as short as possible. Do not install the wires along the 200-400V power line.
Separately install them at a distance of more than 30cm. (Intersecting as applicable.)
If the wires are installed along the power line, put the wires in a metal tube and connect a wire to an end for
grounding. The maximum wiring length is 70m.
In the case that this function is used, it is recommended that safety devices such as electric leakage
breaker or smoke detector, etc. be used.
4.2.4 Power Supply ON/OFF 1 (Automatic Operation When Power Supply ON)
Set the optional function of the remote control switch as shown in the item 4.4.5 (22) to start and stop the
system automatically according to the power supply ON/OFF.
When this function is utilized in the condition that there is no person to operate the unit, make the system
with monitoring for disaster prevention.
NOTE:
The unit is started and stopped according to the power supply ON/OFF due to the power failure.
When the power failure is occurred during operation, the unit is started again automatically after the power
supply is recovered.
Remote Control Switch is required for this function.
4.2.5 Power Supply ON/OFF 2 (Restarting Function After Power Failure)
Set the optional function of the remote control switch as shown in the item 4.4.5 (24) to restart the system
automatically even if power failure continues for more than 2 seconds. Set it after the main switch is OFF.
The standard setting provides automatic restarting in less than 2 seconds after a power failure.
The compressor starts in 2 seconds after a 3 minute time guard after power failure.
NOTE:
The system does not start if the system is stopped before power failure.
Remote Control Switch is required for this function.
Manufacturer or Specifications
Remarks
Auxiliary Relay (X1, X2)
OMRON Mini Power Relay
Model: MY1F or Equivalent
Changeover Switch (SS2, SS3)
Manual Type
3P Connector Cord
Optional Part PCC-1A
(Able to Connect JST Connector XARP-3)
Five Cords with
Connectors as one set
Low Voltage
0.3mm
2
less than 12V
220V/240V Class
0.5 to 0.75mm
2
Low Voltage
0.5 to 0.75mm
2
less than 12V
220V/240V Class
2mm
2
Component
Voltage
220V or 240V
Cord
(Indoor)
Cord
(Outdoor)