TROUBLESHOOTING
Problem
Causes
Solution
No Restarting of
Outdoor Fan Motor
and Compressor
after Stoppage
for Cooling
Operation (Lamp
of “RUN” Switch
and Indicator is
Flickered)
Tripped High Pressure
Switch
•
Obstacle to Air Intake of Air Discharge
for Outdoor Unit
•
Remove the obstacle
•
Insufficient Air Intake or Air Discharge
Space for Outdoor Unit
•
Keep the minimum Air Intake and Air Discharge Space
•
Short Circuited Air Discharge for
Outdoor Unit
•
Remove Any Obstacle
•
Faulty Outdoor Fan Motor
•
Replace the Outdoor Fan Motor
•
Overcharged Refrigerant
•
Charge Correct Refrigerant Gas
•
Clogged Capillary Tube
•
Replace the Capillary Tube
•
Excessively High Ambient
Temperature
•
See Unit Working Range
•
Temperature of High Air Inlet
Temperature for Indoor Unit
•
•
Reduce the Cooling Load
•
Tripped Overcurrent
relay for Compressor
Motor
•
Excessively High Discharge or Suction
Pressure
•
Same as Tripped High Pressure Switch Remedy Action
•
High or Low Voltage
•
Obtain Correct Voltage
•
Faulty Compressor Motor (After
Checked Electrical Resistance)
•
Replace the Compressor
•
Faulty Overcurrent Relay
•
Replace the Overcurrent Relay
•
Faulty Starting Relay
•
Replace the Starting Relay
•
Frequent start/stop compressor
•
Replace the compressor
•
Insufficient Cooling
(Lamp of “RUN”
Switch activates)
Excessive Cooling Load
•
Reduce the Cooling Load
•
Too Low Pressure
•
Insufficiently Charged Refrigerant Gas
•
Charge Correct Refrigerant Gas
•
Refrigerant Gas Leakage
•
Repair Leakage and Charge Correct Refrigerant Gas
•
Clogged Strainer
•
Repair or Replace the Strainer
•
Clogged Suction Piping
•
Remove the Obstacle
•
Clogged Air Filter
•
Cleaning the Air Filter
•
Obstacle to Air Intake or Air Discharge
for Indoor Unit
•
Take Away the Obstacle
•
Faulty Indoor Fan Motor
•
Replace the Indoor Fan Motor
•
Short Circuited Air Discharge for
Indoor Unit
•
Take Away any Obstacle
•
Excessively High
Pressure
•
Same as Tripped Air Discharge for
Indoor Unit
•
Same as Tripped High Pressure Switch Remedy Action
•
Insufficient Heating
(Lamp of “RUN”
Switch Activates)
(Only for Heat-
Pump Models)
Too Low Pressure
•
Clogged Strainer
•
Repair or Replace the Strainer
•
Clogged Suction Piping
•
Remove the Obstacle
•
Obstacle to Air Intake or Air Discharge
for Outdoor Unit
•
Take away the obstacle
•
Faulty Outdoor Fan Motor
•
Replace the Outdoor Fan Motor
•
Short Circuited Air Discharge for
Outdoor Unit
•
Take Away any Obstacle
•
Faulty Thermistor(s) for Deicer
•
Replace the Thermistor(s)
•
Excessively High
Pressure
•
Same as Tripped Air Discharge for
Indoor Unit
•
Same as Tripped High Pressure Switch Remedy Action
•
Содержание RCD-2.0FSNE
Страница 2: ......
Страница 5: ......
Страница 6: ......
Страница 12: ......
Страница 48: ......
Страница 84: ......
Страница 120: ......
Страница 156: ......
Страница 192: ......
Страница 228: ......
Страница 264: ......
Страница 300: ......
Страница 336: ......
Страница 372: ......
Страница 373: ......
Страница 374: ...PMML0126A rev 3 06 07 Printed in Spain ...