Notes:
(1) If the room temperature is (cooling preset temperature) - (1.33°C) or less after 30 seconds from starting the operation, the operation is done assuming as the preset temperature = (room
temperature at the time) - (2°C).
(2) The indoor fan is operated in the “Lo” mode. During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute.
(3) When the operation is started by the themostat turning ON, the start of the indoor fan is delayed 32 seconds after the start of compressor operation.
(4) The compressor is operated forcedly for 3 minutes after operation is started.
(5) The minimum ON time and OFF time of the compressor are 3 minutes.
Содержание RAM-36NP2A
Страница 45: ... 43 MODEL RAI 25RPA RAI 35RPA RAI 50RPA WIRING DIAGRAM INDOOR UNIT ...
Страница 46: ...Remote Control CIRCUIT DIAGRAM 45 ...
Страница 47: ...CIRCUIT DIAGRAM MODEL RAI 25RPA RAI 35RPA RAI 50RPA 47 ...
Страница 48: ... 49 ...
Страница 49: ... 51 ...
Страница 52: ... 57 ...
Страница 54: ... 61 ...
Страница 56: ... 65 ...
Страница 57: ... 67 ...
Страница 62: ... 73 ...
Страница 69: ... 80 ...
Страница 70: ... 81 ...
Страница 72: ... 83 1 Power does not come on no operation CHECKING INDOOR UNIT ELECTRICAL PARTS ...
Страница 74: ... 85 ...
Страница 75: ... 86 ...
Страница 76: ... 87 HOW TO CHANGE THE SHIFT VALUE for SETTING TEMPERATURE USING WIRED REMOTE CONTROLLER ...
Страница 77: ... 88 ...
Страница 78: ... 89 ...
Страница 79: ... 90 ...
Страница 80: ... 91 CHECKING THE REMOTE CONTROLLER ...
Страница 81: ... 92 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAI 25RPA RAI 35RPA RAI 50RPA ...
Страница 85: ... 96 MODEL RAI ECPP PANEL ...
Страница 87: ...HITACHI PM NO 0530E Printed in Malaysia RAI 25RPA RAI 35RPA RAI 50RPA ...