4. Failure phenomenon: The fan motor will not stop.
>
Situation
@
I have conducted the stop operation on the product by remote control, but the indoor fan motor will not stop.
(It stopped about 10 minutes later.)
>
Estimated failure locations
@
·
Indoor fan motor
·
Fan motor drive circuit
>
Diagnosis flow
@
Initiating troubleshooting
Yes
Replace the "indoor fan motor".
No
Replace the "indoor electrical parts".
Run the product by remote control and then stop it.
(Reproduce the failure phenomenon.)
Is the voltage between pins
ĺ
and
ļ
of the fan motor
connector (CN2) below 1.5 V? (Take measurements
while the failure phenomenon is present.)
75
Содержание RAK-15QEF
Страница 2: ... DANGER 2 ...
Страница 21: ...WIRING DIAGRAM MODEL RAK 15QEF RAK 18 25 35 50REF RAK 18 25 35 50REFC 21 ...
Страница 22: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 7PE1 22 ...
Страница 23: ...CIRCUIT DIAGRAM MODEL RAK 15QPE RAK 18 25 35 50REF RAK 25 35 50REFC AX 17H725 ...
Страница 24: ...BLOCK DIAGRAM MODEL RAK 15QEF RAK 18 25 35 50REF RAK 25 35 50REFC Humidity Sensor AX17H725V13 Frost wash 24 ...
Страница 25: ...31 33 29 MODEL RAK 15QPE RAK 18 25 35 50REF RAK 25 35 50REFC 25 ...
Страница 38: ...MODEL RAK 15QEF RAK 18 25 35REF RAK 25 35REFC 38 ...
Страница 39: ...MODEL RAK 50REF RAK 50REFC 39 ...
Страница 42: ...DESCRIPTION OF MAIN CIRCUIT OPERATION MODEL RAK 15QEF RAK 18 25 35 50REF RAK 25 35 50REFC 42 ...
Страница 48: ...10 10 10 10 10 DSW1 48 ...
Страница 52: ...RL1 RL1 RL2 52 ...
Страница 64: ...ON OFF ON OFF ON OFF 3 and page 3 8 9 64 ...
Страница 65: ...DISPLAY OPERATION MODE SETTING ON OFF 65 ...
Страница 66: ... FAN SPEED POWERFUL FAN SPEED POWERFUL HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING 66 ...
Страница 82: ...JCH WH NO 0131E RAK 15QEF RAK 18REF RAK 25REF RAK 50REF RAK 25REFC RAK 35REFC RAK 35REF RAK 50REFC 82 ...