1. Failure phenomenon: The power will not become turned on.
>
Situation
@ǂ
Neither initialization, remote control, nor any other step works on the vane position at power-on.
[ Estimated failure
locations ]
·
3.15 A fuse blown out
·
Control power circuit
·
Connector loose, wire break
>
Cautions
@
>
Diagnosis flow
@
Initiating troubleshooting
Is a voltage of
2
0 V applied between WR2-WR4?
ǂǂǂǂǂǂǂǂǂ
Is the CN16 securely connected?
Replace the "indoor electrical parts".
Replace the "indoor electrical parts".
Replace the "3.15 A fuse".
Replace the "varistor (VA001)".
Abnormal
Is the power supply voltage normal?
Has the varistor VA001 not become burned?
Normal power supply voltage: AC 230 V
Estimated cause of fuse blowout
·
Abnormally high voltage applied to the power supply
·
Indoor fan motor out of order
·
Power circuit out of order
·
Before work, check the power supply voltage. An abnormal voltage may be being supplied in
some rare occasions due to a defect in the indoor wiring (a wire break in the neutral wire of the
single-phase 3-wire power supply).
·
If the 3.15 A fuse has blown out, eliminate the cause of the fuse blowout. Otherwise, there will occur
another fuse blowout.
·
If the 3.15 A fuse has blown out due to an abnormally high voltage to the power supply, the varistor
(VA001) will deteriorate and become destroyed as well.
·
On a repair service visit due to the failure phenomenon of "The power will not become turned on",
take a "3
A fuse" and a "varistor" with you.
Get the indoor wiring back to its
normal condition, then conduct
a final check.
Normal
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Replace the 3.15 A fuse, disconnect the CN2
(indoor fan motor), and conduct an operation
check. Has the product worked?
Replace the "indoor fan motor".
Another fuse blowout
Disconnect the CN2 and check for continuity
between the "red" and "black" wires of the
indoor fan motor by using a tester. Is it short-
circuited?
Apply the black lead of the tester to the red
lead of the motor. Apply the red lead of the
tester to the black lead of the motor.
Replace the "indoor electrical
parts".
Replace the "indoor fan motor".
Replace the "indoor electrical
parts".
Reconnect the connector correctly.
3
AC
.15
Is DC 5 V applied to both ends of the C106?
70
Содержание RAK-15QEF
Страница 2: ... DANGER 2 ...
Страница 21: ...WIRING DIAGRAM MODEL RAK 15QEF RAK 18 25 35 50REF RAK 18 25 35 50REFC 21 ...
Страница 22: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 7PE1 22 ...
Страница 23: ...CIRCUIT DIAGRAM MODEL RAK 15QPE RAK 18 25 35 50REF RAK 25 35 50REFC AX 17H725 ...
Страница 24: ...BLOCK DIAGRAM MODEL RAK 15QEF RAK 18 25 35 50REF RAK 25 35 50REFC Humidity Sensor AX17H725V13 Frost wash 24 ...
Страница 25: ...31 33 29 MODEL RAK 15QPE RAK 18 25 35 50REF RAK 25 35 50REFC 25 ...
Страница 38: ...MODEL RAK 15QEF RAK 18 25 35REF RAK 25 35REFC 38 ...
Страница 39: ...MODEL RAK 50REF RAK 50REFC 39 ...
Страница 42: ...DESCRIPTION OF MAIN CIRCUIT OPERATION MODEL RAK 15QEF RAK 18 25 35 50REF RAK 25 35 50REFC 42 ...
Страница 48: ...10 10 10 10 10 DSW1 48 ...
Страница 52: ...RL1 RL1 RL2 52 ...
Страница 64: ...ON OFF ON OFF ON OFF 3 and page 3 8 9 64 ...
Страница 65: ...DISPLAY OPERATION MODE SETTING ON OFF 65 ...
Страница 66: ... FAN SPEED POWERFUL FAN SPEED POWERFUL HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING 66 ...
Страница 82: ...JCH WH NO 0131E RAK 15QEF RAK 18REF RAK 25REF RAK 50REF RAK 25REFC RAK 35REFC RAK 35REF RAK 50REFC 82 ...