2.Failure phenomenon: The product will not receive a remote control signal.
>
Situation
@ǂ
The product does not receive a remote control signal. It is not very responsive.
(The product does run normally in response to the emergency operation switch.)
>
Estimated failure
locations
@
·
Remote control failure, remote control low battery level, remote control poorly set
·
Remote control light-receiving unit
·
Connector loose, wire break
·
Normal product (external factors: the remote control units for lighting equipment and other
equipment, electrical noise, etc.)
>
Cautions
@
>
Diagnosis flow
@
Initiating troubleshooting
·
Even if the product is trouble-free, a factor coming from outside the product may hamper the
reception of signals from the remote control unit.
·
Batteries may decline in capacity at low temperatures. Old batteries decline particularly much in
voltage in the morning and evening of winter, resulting in the poor arrival of remote control signals.
Instruct your users to use new alkaline batteries.
Does the remote control unit have a sufficient battery capacity?
If the liquid crystal display becomes
extremely faded when a remote control
signal is sent, replace the batteries.
No
Press the reset switch of the remote control unit,
then conduct another operation check.
Has the product worked?
Yes
Instruct your users to be sure to press
the reset switch after replacing the
batteries.
Yes
Did you identify a failure phenomenon?
Go on to "how to identify sources of
jamming in the reception of remote
control signals" .
No
Yes
Conduct an operation check according to "checking the remote
control".
Is the remote control normal?
No
Yes
Replace the "remote control unit".
No
Is the CN16 securely connected?
Yes
Reconnect the connector correctly.
Yes
Check for jamming due to an external factor while referring to
"how to identify sources of jamming in the reception of
remote control signals".
Is there jamming from outside?
Cope with jamming according to its cause.
No
No
Replace the "indicating P.W.B".
Cautions in replacing the indicating P.W.B
Be sure to replace the indicating P.W.B. components.
116
Содержание RAC-18WPB
Страница 50: ...WIRING DIAGRAM RA RAC 18 25 35WPB K 18 25 35 50PPB RAC 5 WPB 0 50 ...
Страница 52: ...CIRCUIT DIAGRAM MODEL RAK 18 25 35 50PPB 52 WIRED REMOTE CONTROL SEND POWER FOR CLEANNESS ...
Страница 53: ...MODEL RA C 18 25 35 WPB 53 ...
Страница 54: ...MODEL RAC 50WPB 54 ...
Страница 67: ...MODEL RAK 18 25PPB RAC 18 25WPB INDOOR UNIT INDOOR UNIT 67 ...
Страница 68: ...COOLING CYCLE INDOOR UNIT OUTDOOR UNIT HEATING CYCLE INDOOR UNIT OUTDOOR UNIT MODEL RAK 35PPB RAC 35WPB 68 ...
Страница 78: ...10 10 10 10 10 R901 R904 R641 R907 R908 R694 R902 R695 R741 R740 R642 DSW1 DSW1 R903 R905 R906 78 ...
Страница 81: ...L N 300 330 Main parts L N C021 C022 37 5 420V RAC 18 25 35WPB 81 1 5 ...
Страница 85: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 85 ...
Страница 86: ...6 Electric expansion valve circuit 48 47 46 45 13 14 15 16 4 3 2 1 68 67 66 65 RED 14 12 10 7 6 1 8 6 1 6 2 86 ...
Страница 87: ...2A Fuse DC300 330V 7 7 1 87 ...
Страница 88: ...2A DC300 330V 88 ...
Страница 89: ...L N 300 330 L N 50WPB 89 ...
Страница 90: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 90 ...
Страница 94: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 94 ...
Страница 96: ...2A Fuse DC300 330V 7 1 7 96 ...
Страница 97: ...2A DC300 330V 97 ...
Страница 108: ...108 109 ...
Страница 110: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25 35WP B 110 ...
Страница 111: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50WP B 111 ...
Страница 131: ...57 131 ...
Страница 132: ...Please set the DIP switch No 6 to ON accordingly Refe to page r 78 132 ...
Страница 133: ...78 133 ...
Страница 134: ...134 ...
Страница 148: ...HITACHI RAK 18PPB RAC 18WPB RAK 25PPB RAC 25WPB HHAW NO 0080E RAK 35PPB RAC 35WPB RAK 50PPB RAC 50WPB 3 148 ...