The air deflector control operation shown below is done when the swing switch
is pressed or when the operation mode is changed.
●
The air deflector control operation shown below is done when the operation
switch is turned off.
Item
3-way
AUTO (Swing)
Specification
Cooling/
dehumidi-
fying
Heating
(When the
operation
switch is
turned off
Automatic
shut
operation)
Air
blowing
direction
control
8
Other detailed specifications
1
.
When the room temperature starts to
increase within 3 minutes after thermo
OFF in “cooling” and fan speed “AUTO”,
the fan speed changes L
→
M
→
H as
when thermo ON.
2
.
If “cooling” is selected during “sensor
dehumidification” operation the operation
continues as it is with the thermo ON.
The 3 minutes delay is not started. The
set temperature and fan speed depend
on the remote control signal.
It is same for “cooling” – – – – “sensor
dehumidification”. It is same for “AUTO”
sensor dehumidification cooling “sensor
dehumidification” “cooling”.
3
.
The filter sign lights after 100 hours
operation of the room fan. The lamp goes
out when the POWER SWITCH set to
OFF and ON again.
4.
After the failure mode is started (indicator
lamp flickering), rapid mode changing
cannot be done.
5
.
If the operation is made by the nice
temperature reservation during the sleep
operation, the normal operation
continuously occurs, and for the advance
time, the temperature difference between
the set temperature without sleep shift
and “room temperature” is used.
– 45 –
●
Operation starts in advance so that the room temperature reaches
the preset value at the set time.
●
The operation time is obtained as follows depending on the room
temperature when operation starts.
(1)
Calculation method of the moved-up time.
Moved-up time (MT) = Moved-up time depending on the temperature
difference (OT) + compensation time (HT).
MT is at least 1 minute if OT is not zero.
Heating
Cooling
(MT)
00 ~ 60 min.
00 ~ 60 min.
(OT)
00 ~ 60 min.
00 ~ 60 min.
(HT)
–60 ~ 60 min.
–60 ~ 60 min.
Obtain OT (moved-up time depending on the temperature difference)
from the table below.
10
“NICE
TEMPERA-
TURE”
reservation
Heating
Cooling
Setting temp.
–
Room temp.
Time (min.)
Setting temp.
–
Room temp.
Time (min.)
00
–
01.00
00
00.00
–
02.00
00
01.25
–
03.00
10
02.25
–
05.00
15
03.25
–
07.00
20
05.25
–
08.00
30
07.25
–
10.00
30
08.25
–
11.00
45
10.25
–
13.00
40
11.25
–
6
0
13.25
–
16.00
50
16.25
–
19.00
60
19.25
–
22.00
60
22.25
–
❈
The preset temperature value shown above does not
include any shift value.
(2
)
Compensation
1
The “Attained” state is monitored and a “Not attained” check is
done to revise the compensation time (HT).
“Attained” monitor
Continuously monitored during “NICE TEMPERATURE” operation.
(Heating)
When the room temperature < Set value + compensation shift, it
is regarded to be “attained” and 5 minutes are reduced from the
compensation time.
(Cooling)
When the room temperature < Set value + compensation shift, it’s
operated same as above.
“Not attained” check
Performed once when the “NICE TEMPERATURE” timer is completed.
(Heating)
When the room temperature < Set value + compensation shift 1
°
C,
it is regarded to be “Not attained” and 5 minutes are added to the
compensation time.
(Cooling)
When the room temperature > Set value + compensation shift
+1
°
C, it’s operated same as above.
❈
If the room temperature is 1
°
C from the set value +
compensation shift, compensation is not done.
Item
ON temperature
Thermostat operation
(Thermostat relay)
power relay (
°
C)
Differential (
°
C)
Low-temperature defrosting
Cooling, sensor
dehumidification
(T1)
RAS-07/09/14GH4
16
16.6
24
24.6
32
32.6
0.33
ON (
°
C)
1.0
Reset (
°
C)
12.0
Table 2 Sensor operation values
Item
RAS-07/09/14GH4
Automatic
Yes
Heating
Yes
Operation switching
Sensor dehumidification
Yes
Cooling
Yes
Fan
Yes
Temporary switch
Yes (automatic)
Service switch
Cooling
Yes
Nice temperature reservation
Yes
Defrosting
Yes
Sleep circuit
Yes
Heater operation at the time of sensor dehumidification
No
Automatic blowing direction
Yes
Filter sign
Yes
Wireless mode
Heat and Cool wireless
Table 1 Specifications
Down
Up
Down
Up
❈
Swing start direction
Down
Up
❈
Swing start direction