INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2>

1

1.

 

INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2>

 DANGER:

§

 

DO NOT pour water into the remote controller (hereafter
called “controller”).  These products are equipped with
electrical parts.  If poured, it will cause a serious electrical
shock.

§

  DO NOT operate switches by wet hand.  It may cause an

electrical shock.

§

  In case that the protective devices often function or the

operation switches do not function well, turn OFF the main
power supply and contact your distributor or dealer of
HITACHI.

§

  In case that other abnormalities are found, stop the system,

turn OFF the main power supply and contact your distributor
or dealer of HITACHI.

 WARNING:

§

  DO NOT perform installation work and electrical wiring

connection by yourself.

§

  In case that a service work such as repair, maintenance, etc.

is required, contact your distributor or dealer of HITACHI.

§

  DO NOT modify the electrical wiring.  It may cause serious

accidents.

 CAUTION:

§

  DO NOT install the controller and cable at such places as;

(1) where there is oil vapor and the oil is dispersed.
(2) where the hot springs are near (in a sulfuric

environment).

(3) where generation, flowing, staying or leaking of

flammable gas is detected.

(4) where the sea is near (in the salty environment).
(5) an acid or alkaline environment.

§

 

DO NOT install the indoor unit, outdoor unit, controller and
cable within approximately 3 meters from strong
electromagnetic wave radiators such as medical equipment.

§

  DO NOT use the multi-core wire for electrical wiring.

If used, some signals of one system transfer to the other
system, the signals interfere each other and it cause the
malfunction.

§

  DO NOT use thin shield wire such as CPEVS. Such wires

with big electrostatic capacity make the transmission signal
dull end the transmission error may occurs in case of long
distance wiring.

§

  DO NOT run any cable for transmission and signal along the

power line (220-240V, 380-415V).

§

  DO NOT run any cable for transmission and signal along

other cables for transmission and signal.
If the cables are required to be run along, keep a distance
more than 30 cm between each cables, or insert the cables
for each transmission system into the metal conduit tube and
ground one end of the conduit tube.

n

 

Location of Remote Controller

1. Select a suitable place for handling and determine the

installation place of the controller with the customer’s
acceptance.
Do not install the controller at such places as;

§

 

where children can touch

§

 

where the air from the air conditioner is directly
discharged

§

 

where there is oil vapor and the oil is dispersed

§

 

where the humidity is high.

Especially in case that a remote control thermostat is used,
select the installation place in consideration with the
following points;

§

 

where the average room temperature can be detected

§

 

where the thermostat is not exposed directly to the sun

§

 

where the heat sources is not near around

§

 

where the thermostat is not affected with the outdoor air
by opening and closing doors

§

 

where the air from the air conditioner is directly
discharged

2. Pay attention to the following points in case that the

controller is installed in a place where there is medical
equipment radiating electromagnetic waves.

§

 

DO NOT install the controller in a place where
electromagnetic waves are radiated directly toward the
remote control cable and the controller.

§

 

Keep a distance more than 3 meters away from the
equipment radiating electromagnetic waves.

§

 

Keep a distance more than 3 meters away from the
receiver such as radio. It may cause noises.

§

 

Shield the controller and cables by covering with the steel
box and running the cable through the metal conduit tube.

§

 

In case that there is electric noise at the power source for
the indoor unit, provide a noise filter.

§

 

In case of installing the wireless remote control switch
onto the wall, keep a distance more than 30 cm from the
power line.

Содержание PC-2H2

Страница 1: ...onsultazioni Leia e compreenda este manual antes de operar este ar condicionado Guarde este manual para futura referencia De bor laese og forsta denne vejledning for de tager dette dlimaanlaeg i brug Opbervar vejledningen til senere reference Lees deze hadleiding aandachtig door alvorens de airconditioning in gebruik te nemen Läs och första denna manual innan Du sätter igang luftkonditioneraren Fö...

Страница 2: ......

Страница 3: ...run any cable for transmission and signal along the power line 220 240V 380 415V DO NOT run any cable for transmission and signal along other cables for transmission and signal If the cables are required to be run along keep a distance more than 30 cm between each cables or insert the cables for each transmission system into the metal conduit tube and ground one end of the conduit tube n Location ...

Страница 4: ...f the holding bracket push and turn the screwdriver and remove the controller from the holding bracket as shown in the figure below Fig 2 Installation Procedure Fig 3 Installation Procedure 2 Attach the controller to the holding bracket as follows A In case of exposing Remote Control Cable É Fix the holding bracket onto the wall as shown below Fig 4 Attach the controller Ê Make the hole for drawin...

Страница 5: ...nting work is finished Fig 10 Mounting procedures CAUTION Pay attention so that the cable may not be slack If the cable is slack as shown in the above figure the cable cord especially the naked part may be clamped at the hole and it may cause a faulty operation 1 4 WIRING SYSTEM FOR REMOTE CONTROL SWITCH PC 2H2 1 4 1 LENGTH OF WIRE CABLE FOR REMOTE CONTROL SWITCH Length of the standard wire cable ...

Страница 6: ...wires B After checking the color of the wires connect each wire of the same color by soldering C Insulate the soldered parts and the wires with insulation tape D The maximum total cable length of the remote control switch cable and the bridge cable s is 200 meters 0 3mm2 wire or 500 meters 0 75mm2 wire 3 Separate the cable more than approximately 30cm from any wires which are utilized for wires hi...

Страница 7: ... Bridge Cable 9 Contact of Connectors of Bridge Cable Ë Back to É after checking Ì Select TEST RUN MODE by depressing MODE Switch COOL OR HEAT Í Depress RUN STOP switch a The TEST RUN operation will be started The TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again b IF the unit do not start or the operation lamp on the remote control switch ...

Страница 8: ...pressor Heat Pump Twin 11 Thermistor Abnormality for inlet Air Temperature All Models 12 Thermistor Abnormality for outlet Air Temperature Heat Pump Twin 13 Thermistor Abnormality for Freezing Temperature All Models 20 Thermistor Abnormality for Compressor Top Temperature Heat Pump Twin 22 Thermistor Abnormality for Outdoor Air Temperature Heat Pump Twin 24 Thermistor Abnormality for Outdoor Evapo...

Страница 9: ...etting temperature is turned OFF b At the condition of the above item a press the TEMP switch or the TEMP switch of the remote control switch and the indoor unit for which the optional function is to be set can be changed NOTES The indoor unit can be selected among the indoor units connected to the remote control switch In case that both the indications of the address and the refrigerant cycle num...

Страница 10: ...0 01 Not Available Available b4 Change of Filter Cleaning Time 00 01 02 03 04 Standard 100 hours 1200 hours 2500 hours Not Indication b5 Fixing of Operation Mode 00 01 Not Available Available b6 Fixing of Setting Temperature 00 01 Not Available Available b7 Fixing of Operation as Exclusive Cooling Unit 00 01 Not Available Available b8 Automatic COOL HEAT 00 01 Not Available Available b9 Fixing of ...

Страница 11: ......

Страница 12: ...PMML0041B 12 01 Printed in Spain ...

Отзывы: