1 SPECIFICATIONS
1-2
1.1 Use
The CPU link module (Model LQE550) is a communications module that provides inter-CPU
data exchange.
When this module (Model LQE550) is used with the S10mini’s CPU unit, it is allowed to coexist
with the Model LQE050 CPU link module, which is specially designed for use with the S10mini
(the LQE050 cannot be used with the S10V’s LPU unit).
1.2 Specifications
Table 1-1 CPU Link Module Specification
Item Specifications
Module type
LQE550
Number of CPU link modules
mounted
S10mini: Up to 2/CPU (main link and sublink)
S10V: Up to 2/LPU (main links and sublinks)
Number of CPUs linked
Up to 16/link line (main links and sublinks)
Data transfer area (*)
G000 to GFFF (4,096 locations)
Data output area
Up to 1,024 locations/unit (must be unique across all units)
Link cable
Total extension
of up to 1 km
Characteristic impedance: 150
Ω
(at 500 kHz)
Attenuation: 8.5 dB/km (at 500 kHz)
Recommended cable type: CO-EV-SX 1P×0.75 mm
2
Hitachi Cable, Ltd.
Terminal register: 150
Ω
Characteristic impedance: 150
Ω
(at 500 kHz)
Attenuation: 7.8 dB/km (at 500 kHz)
Recommended cable type: CO-EV-SB 1P×0.3 mm
2
Hitachi Cable, Ltd.
Terminal register: 150
Ω
Total extension
of up to 600 m
Characteristic impedance: 100
Ω
(at 500 kHz)
Attenuation: 12 dB/km (at 500 kHz)
Recommended cable type: CO-SPEV-SB 1P×0.5 mm
2
Hitachi Cable, Ltd.
Terminal register: 100
Ω
Total extension
of up to 300 m
Characteristic impedance: 100
Ω
(at 500 kHz)
Attenuation: 17 dB/km (at 500 kHz)
Recommended cable type: CO-SPEV-SB 1P×0.3 mm
2
Hitachi Cable, Ltd.
Terminal register: 100
Ω
Terminal block
18 points (M3 screws), connector type
(*) The main links and the sublinks share the data transfer area.
NOTICE
Use only one type of cable to wire each line. Use of different types of cable in a
single CPU link line may cause invalid data to be transmitted or received or cause
communication errors.
Содержание LQE550
Страница 1: ......
Страница 2: ......
Страница 17: ...This Page Intentionally Left Blank ...
Страница 19: ...This Page Intentionally Left Blank ...
Страница 28: ...1 SPECIFICATIONS ...
Страница 34: ...2 NAMES AND FUNCTIONS OF EACH PART ...
Страница 38: ...3 MOUNTING AND WIRING ...
Страница 46: ...4 OPERATION ...
Страница 75: ...4 OPERATION 4 30 Figure 4 33 An Example of a CPU Link Parameters Output in CSV Format ...
Страница 79: ...This Page Intentionally Left Blank ...
Страница 80: ...5 PROGRAMMING ...
Страница 88: ...6 MAINTENANCE ...