4-43
Multi-speed operation function
It is possible to set multiple operation speeds and switch between the
speeds with the terminals.
Multi-speed operation can be selected by binary operation(max. 16
speeds) with 4 terminals or by bit operation (max. 6 speeds) with 5
terminals.
Set item
Functin code
Set value
Description
00
Change to binary operation 16 speed.
Multi-speed
selection
A019
01
Change to bit operation 6 speed
Multi-speed
0-15
A020/A220-A035
0.00, start frequency-
max. frequency
Units:Hz
(1) Binary operation
It is possible to set multi-speed 0 to 15 by selecting 02 to 05 (CF1 to CF4) on the intelligent input terminals.
Set frequency setting for speed 1 to 15 with A021-A035.
Set 0 speed with A020/A220 or F001 when frequency command is operator.
Or when frequency command is control terminal (Terminal), set with O, OI, O2 terminal.
Multi-speed
CF4
CF3
CF2
CF1
0 speed
OFF
OFF
OFF
OFF
1 speed
OFF
OFF
OFF
ON
2 speed
OFF
OFF
ON
OFF
3 speed
OFF
OFF
ON
ON
4 speed
OFF
ON
OFF
OFF
5 speed
OFF
ON
OFF
ON
6 speed
OFF
ON
ON
OFF
7 speed
OFF
ON
ON
ON
8 speed
ON
OFF
OFF
OFF
9 speed
ON
OFF
OFF
ON
10 speed
ON
OFF
ON
OFF
11 speed
ON
OFF
ON
ON
12 speed
ON
ON
OFF
OFF
13 speed
ON
ON
OFF
ON
14 speed
ON
ON
ON
OFF
15 speed
ON
ON
ON
ON
(2) Bit operation
It is possible to set multi-speed 0 to 5 by assigning 32 to 38 (SF1-SF7) to the intelligent input terminals.
Set frequency SF1-SF7 to A021-A027.
Multi-speed
SF7
SF6
SF5
SF4
SF3
SF2
SF1
0 speed
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1 speed
-
-
-
-
-
-
ON
2 speed
-
-
-
-
-
ON
OFF
3 speed
-
-
-
-
ON
OFF
OFF
4 speed
-
-
-
ON
OFF
OFF
OFF
5 speed
-
-
ON
OFF
OFF
OFF
OFF
6 speed
-
ON
OFF
OFF
OFF
OFF
OFF
7 speed
ON
OFF
OFF
OFF
OFF
OFF
OFF
When each terminal turns ON simultaneously, the lower
number has priority. In order for the inverter to operate both
the frequency and the RUN operation (FW,RV) must be applied.
The L300P series can allocate it to 5 biggest terminals simultaneously.
Chapter 4 Explanation of function
A019: Multi-speed selection
A020/A220: 1st/2
nd
/multi-stage speed
zero speed
A021-A035: Multi-speed 1-15
C001-C005: Intelligent input terminal
Relation code
2 speed
1 speed
11 speed
3 speed
5 speed
6 speed
7 speed
4 speed
8 speed
9 speed
10 speed
12 speed
13 speed
14 speed
15 speed
0 speed
Frequency command from
operator or analog external
input terminal.
CF1
CF2
CF3
CF4
FW
1 speed
SF1
SF2
SF3
SF4
SF5
FW
0 speed
1 speed
2 speed
3 speed
4 speed
5 speed
Frequency command from
operator or analog external
input terminal
Содержание L300P-1100H
Страница 127: ...6 3 Chapter 6 Specification 6 2 Dimension L300P 110 150LF HF L300P 185 300LF HF ...
Страница 128: ...6 4 Chapter 6 Specification L300P 370LF HF L300P 450 550LF HF 750HF ...
Страница 129: ...6 5 Chapter 6 Specification L300P 750LF L300P 900H 1100H ...
Страница 130: ...6 6 Chapter 6 Specification L300P 1320HF ...