5-5
5.6 Capacitor Life Curve
(Note 1)
Ambient air temperature means the surrounding temperature of the inverter. In case the inverter is
installed in a cabinet, ambient air temperature is the temperature of the internal air of the cabinet.
(Note 2)
DC bus capacitors are recommended to be replacing every 5 years. And if the inverter is used in a worse
condition, this recommended replacing period is reduced.
Chapter 5 Maintenance, Inspection
10
20
30
40
1
Ambient temperature (ºC)
50
0
-10
2
3
4
5
6
7
8
9
10
Life time (year)
12h/day operation
24h/day operation