L100-M Inverter
27
Force Operation from Digital Operator
This function permits a digital operator interface to override the Run command source
setting (A_02) when it is configured for a source other than the operator interface. When
the [OPE] terminal is ON and the operator interface gives a Run command, the inverter
uses the standard output frequency settings to operate the motor.
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
31
OPE
Force Operation from
Digital Operator
ON
Forces the operator interface Run command to
over-ride commands from input terminals (such
as [FW], [RV]).
OFF
Run command operates normally, as configured
by A_02
Valid for inputs:
C_01, C_02, C_03, C_04,
C_05
Required settings:
A_01
A_02 (set not equal to 02)
Notes:
•
When changing the [OPE] state during Run Mode
(inverter is driving the motor), the inverter will stop
the motor before the new [OPE] state takes effect.
•
If the [OPE] input turns ON and the digital operator
gives a Run command while the inverter is already
running, the inverter stops the motor. Then the
digital operator can control the motor.
Example (requires input configuration—
see Chapter 3 in L100 Instruction Manual):
See I/O specs in the L100 Instruction Manual
1
2
3
4
5
L
P24
OPE
for
-MFR2
models
for
-MFU2
models