L100-M Inverter
15
Configuring Drive Parameters
This section provides details for L100-M Series configuration corresponding to
Chapter 3, “Configuring Drive Parameters,” in the L100 Inverter Instruction Manual.
Relative to standard L100 Series inverters, Hitachi L100-M Series inverters have
additional parameters and functions, or parameters with a different setting range. These
include D_16, F_04, B_12, B_13, B_32, C_01 to C_05, C_70, C_71, C_72, and C_79.
The tables in this section list only these parameters as they apply to L100-M Series
inverters.
“D” Group: Monitoring Functions
L100-M Series inverters add the following to the monitoring functions.
“F” Group: Main Profile Parameters
For parameter F_04, L100-M Series inverters have the additional “02 Terminal” setting.
With F_04=02, the inverters use [FW] and [RV] inputs in real time to determine the
direction of rotation for the keypad Run key. For more information on Run key operation
and interaction with [FW] and [RV] terminals, see page “Forward Run/Stop and Reverse
Run/Stop Commands:” on page 23.
“D” Function
Run
Mode
Edit
Range and Units
Func.
Code
Name /
SRW Display
Description
D_16 Cumulative operation
RUN time monitor
Displays total time the inverter
has been in RUN mode in
hours.
—
0 to 9999 / 1000
to 9999/
100 to 999
(10,000 to 99,900)
hrs.
RUN 0000000hr
“F” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–MFU2
–MFR2
Units
F_04
Keypad Run key routing Two options; select codes:
00 ...Forward
01 ...Reverse
02 ...Terminal
✘
00
00
—
INIT DOPE FWD